AEG 1000 Manuel D’Utilisation

Page de 76
 
 
23 
EN 
The original carton provides effective protection against damage 
and should be kept in case the device has to be transported 
again at a later date. 
Always keep plastic bags away from babies and children to 
prevent suffocation. 
Handle the components with care. Think of their weight and have 
a second person to assist with lifting. 
4.2 Installation 
location 
The PROTECT D. is designed to be installed in a protected 
environment. When choosing that location, make sure that there 
is adequate ventilation and other appropriate environmental 
conditions. 
 
The PROTECT D. is air-cooled. Do not block the 
vents! 
The UPS and its battery modules in particular
should preferably be operated at room temperature
(between 15°C and 25°C). 
Install the devices in a room that is dry, relatively dust-free and 
free of chemical vapors. 
Make sure that no magnetic storage media are stored and
 
/ or 
operated in the vicinity of the PROTECT D. 
 
Check the type plate to make sure that the voltage
and frequency specifications match those of your
load segments. 
4.3 Assembly 
For the rack installation of the UPS system and its external 
battery units (special accessory), please note the following: 
•  To prevent vibration and jarring, the installation location has 
to have adequate stability. 
• Make sure the rack is able to support the installation, 
particularly when external battery units (special accessory) 
are used. 
• Install the units so that there is adequate air circulation. 
Make sure there is at least 100 mm of free space behind the