Installation 
 
Please see the diagram on the last page for complete wiring. 
 
The IOM Input/Output module is wired to the controller on the same RS-485 network 
as the DS100 Door stations. The IOMs are addressed using the DIP switches on the 
PCB. The IOMs are maybe given any address in the range 1 to 4. 
 
No configuration of the IOM is possible from the keypad, useful configuration can 
only be performed from ACTWinPro. However the IOM maybe enabled from the 
keypad which allows the communications between the ACT2000/ACT3000 and the 
IOM to be tested without the need for ACTWinPro. 
 
Enabling IOM communications from the keypad. 
 
1. Enter the Installer menu by entering the installer code. The LCD on the controller 
will display “Installer Menu” on the top line and “System Settings” on the lower 
line. 
 
2. Press the “0” key twice “Communications” will be displayed on the bottom line of 
the display. 
 
3. Press the “” key followed by the “0” seven times, now  “Communications IO 
Modules
” will appear on the display. 
 
4. Press the “” and use the “0” key to select IOM address, now press the “” to 
enable the communications. 
 
5. If communications are established the Red LED on the IOM will flash rapidly, 
otherwise the LED will pulse once a second and the ACT2000/ACT3000 will display 
IO Module X Offline”. 
 
The IOM is supported by ACT2000X 4.08 and ACT3000 1.07 and greater 
Firmware versions. 
 
 
 