ADC 70 Manuel D’Utilisation

Page de 32
ADCP-80-524 • Issue 1 • November 2001
Page 4
©
 2001, ADC Telecommunications, Inc.
General Safety Precautions
-
Important Product Features
Both
  the  traditional  and  uninterrupted  fuse  panel  provide  dc  power  over  two  separate  buses
(feeds).
 However, with the uninterrupted fuse panel, when one bus loses input power, the other
bus
 supplies the output power for both buses. 
Application:
 Type 70 series fuse panels are used to supply protected dc power to the various
types
 of telecommunications products typically used in central offices, multimedia headends,
remote
 sites, and other locations.
Input
 Power: Type 70 series fuse panels contain two buses (feeds) that accept –24 Vdc or –48
Vdc
 input power. The traditional fuse panel is rated at 65 Amps input current per bus for a total
output
 current of 130 Amps per fuse panel. The uninterrupted fuse panel is rated at 60 Amps
input
 current per bus but the  total  output current cannot exceed 60 Amps per panel. During
back-up
 operation, the uninterrupted can supply an output current of up to 30 Amps per bus or
one
 half of the 60 Amps input current provided by the working power source. 
Output
 Power: Type 70 series fuse panels provide fuse protected output power with up to 8
fuse
 positions per bus. The selectable current rating for each fuse can be standard amperage
capacity
 type 70 fuses up to 10 Amps.
Type
 70 series fuse panels incorporate several important features:
• Self-configuring
 input voltage (–24 Vdc or –48 Vdc) capability with up to 65 Amps per
bus
 (traditional fuse panel) and 60 Amps per bus (uninterrupted fuse panel) to simplify
installation
 and allow their use in most dc voltage applications
• A
 colored indicator that projects from the center of a blown type 70 fuse to quickly and
easily
 identify the affected fuse position
• Alarm
  contact  connections  built  into  the  fuse  panel  for  connection  to  external  visual,
audio,
 and remote alarms
• Field-replaceable
 high-brilliance Power-On green and Alarm red LED indicators
• Easily-removable
 smoked plastic protective cover over connectors to enhance safety and
panel
 accessibility
• Two-post
 grounding to ensure robust and reliable ground connectivity
Caution:
 The fuse panel uses electrical voltage and amperage levels which, per GR-1089, may
be
  considered  an  electrical  hazard.  Care  should  be  exercised  to  assure  that  only  qualified
personnel
  are  allowed  to  install,  operate,  maintain,  or  otherwise  come  in  contact  with  this
equipment
  when  the  panel  is  energized.  Only  insulated  tools  should  be  used  on  energized
elements
 of the panel.
Caution:
 All fuse panel wiring and cabling should be connected with the system office battery
input
 off or disconnected at the office distribution panel.
Caution:
 A replacement fuse must be the same type and must have exactly the same current
rating
 as the fuse being replaced.