Toshiba profibus-dp pbdp-110 Manuel D’Utilisation

Page de 38
 
 22
Frequency Command 
Drive parameter number FA01.  The data contained in the frequency command word 
is the desired frequency command multiplied by 100, and then converted to 
hexadecimal.  In other words, if a frequency command of 55.34Hz is desired, then 
55.34 x 100 = 5534, which converted to hexadecimal is 0x159E.  The frequency 
command high byte (offset 6 or 22) must therefore contain 0x15, and the frequency 
command low byte (offset 7 or 23) must contain 0x9E. 
 
If the frequency command exceeds limiting drive parameters (such as the upper limit 
frequency), the drive will ignore it, maintaining its current setting. 
 
 
Action Bits / Parameter Number 
Parameter action bits and 16-bit parameter register number.  Refer to section 10 for 
a detailed explanation of these items. 
 
 
Parameter Data 
During parameter register writes, this word contains the data to write.  Refer to 
section 10 for a detailed explanation of this data word 
 
 
Again, in case of any discrepancies, documentation provided by the drive 
manufacturer supercedes the examples given here.