Toshiba profibus-dp pbdp-110 Manuel D’Utilisation

Page de 38
 
 25
Output Frequency 
Drive parameter number FD00.  Continuously reports the drive’s operating frequency.  
In order to determine the drive’s actual output frequency, the data contained in the 
output frequency word offsets must first be converted from hexadecimal to decimal, 
and then divided by 100.  For example, if the output frequency high byte is 0x12 and 
the output frequency low byte is 0x34, then 0x1234 converted to decimal is 4660.  
Dividing this number by 100, the actual operating frequency of 46.60Hz is obtained. 
 
 
Output Current 
Drive parameter number FE03.  Continuously reports the drive’s output current in %.  
In order to determine the drive’s actual output current, the data contained in the 
output current word offsets must first be converted from hexadecimal to decimal, and 
then divided by 100.  For example, if the output current high byte is 0x23 and the 
output current low byte is 0x15, then 0x2315 converted to decimal is 8981.  Dividing 
this number by 100, the actual output current of 89.91% rated drive current is 
obtained. 
 
 
Output Voltage 
Drive parameter number FE05.  Continuously reports the drive’s output voltage in %.  
The actual output voltage calculation method is identical to that for output current 
given above. 
 
 
Action Bits / Parameter Number 
Parameter action bits and 16-bit parameter register number.  Refer to section 10 for 
a detailed explanation of these items. 
 
 
Parameter Data 
During parameter register reads, this word contains the requested data response.  
Refer to section 10 for a detailed explanation of this data word 
 
 
Again, in case of any discrepancies, documentation provided by the drive 
manufacturer supercedes the examples given here.