Checking location of indoor unit number
(1)To find the address of indoor unit whose location is clear
In case of independent operation
(1:1 connection of wired remote controller and indoor unit)
Perform the procedure during operation of indoor unit.
<Procedure>
1
When the indoor unit is not working, push 
ON / OFF
 on the
remote controller.
2
Push 
UNIT LOUVER
 .
UNIT No. 
1-1
 appears on the LCD and disappears in several
seconds.
The displayed number shows the refrigerant line address and
indoor unit address.
When other indoor units are connected to the same remote control-
ler (group control), their unit numbers are displayed in order each
time 
UNIT LOUVER
 is pushed.
(2)To find the location of indoor unit from its address
When checking indoor unit number in the group.
Perform the procedure while the indoor unit is not working.
This procedure stops operation of all indoor units in the group.
<Procedure>
Indoor unit numbers appear one by one and the fan and louver of
the displayed unit run.
1
Push 
TEST
 and 
VENT
 on the remote controller simultaneously
for 4 seconds or more.
• UNIT No. 
  appears.
• The fan and louver of all indoor units in the group run.
2
Each pushing of 
UNIT LOUVER
 on the remote controller displays
unit numbers in the group sequentially.
• The header unit address appears first.
• The fan and louver of a selected indoor unit run.
3
Push 
TEST
 to finish the procedure. Operation of all the indoor
units in the group turns OFF.
END
Operation procedure
1
 → 
2
 → 
3
  END
Operation procedure
1
 → 
2
ON / OFF
FILTER
RESET
VE
G/FIX
VENT
UNIT LOUVER
CODE No.
C
UNIT No.
R.C.
No.
MODE
FAN
ON / OFF
SET
TEST
FILTER
RESET
CL
SAVE
SWING/FIX
VENT
UNIT LOUVER
CODE No.
UNIT No.
R.C.
No.
TIME
MODE
AN
SET DATA
SETTING
1 2
1
3
2
FILE NO. SVM-12004
– 
87
 –