Toshiba reliability in motion 1700 Manuel D’Utilisation

Page de 39
TOSHIBA 
 
12 
Starting on DC Power 
If no AC power source is available, or if the AC input power is 
outside of the allowable range for voltage or frequency, the UPS can 
be started from battery power.  The length of UPS operation time on 
battery power depends on the number of attached battery modules 
and the amount of load the UPS is supporting.  To start the UPS 
from battery power follow these steps: 
 
Step 1:  Make sure the RUN/STOP switch is in the STOP position.  If 
the UPS is being started on DC power because the AC power is out 
of range, the input breaker must be in the OFF position (figure 1, 
page 9). 
 
Step 2:  Press the “Startup on Battery” button.  The UPS will beep 
indicating that AC power is not available and the Startup on Battery 
mode has been activated. 
 
Step 3:  Switch the RUN/STOP switch to the RUN position.  This 
must be done within 5 seconds of the Startup on Battery mode 
activation for the unit to startup using batteries. 
 
Once the unit has started, the “On Line” LED will light, indicating that 
the inverter is running and power is available at the output 
receptacles.  If the RUN/STOP switch is not switched to the RUN 
position within those 5 seconds, the unit will return to shutdown 
mode. 
 
Stopping the UPS 
There are two ways of turning the UPS off:  switching from on line to 
bypass mode, or completely shutting down. 
Option 1:  The first option is to place the UPS into bypass mode.  
Bypass mode means that if there is AC power available, the UPS will 
route power directly from the input source to the connected loads 
without any conditioning.  The UPS inverter is off during this state, 
but the attached loads do not lose power during the transition.  To 
place the UPS into bypass mode, switch the RUN/STOP switch to 
the STOP position.  This mode is most often used manually during 
maintenance and programming operations or automatically upon the 
occurrence of an internal UPS fault.  (For more information 
concerning bypass mode see appendix E.) 
Option 2:  The other option is to turn the UPS off completely.  This 
means that in addition to the UPS’s inverter shutting down, all power 
will be stopped to any equipment attached to the UPS
.  To shut 
the UPS down completely switch the RUN/STOP switch to the STOP 
position.  Then switch the input breaker off (figure 1, page 9).  Once 
the input breaker has been switched off, all the LEDs should turn off.  
(If the RUN/STOP switch is in the RUN position when the input 
breaker is switched off, the unit will switch to battery backup mode.  
The unit will continue to run for as long as the available battery 
reserves can support the connected loads.)