Toshiba reliability in motion 1700 Manuel D’Utilisation

Page de 39
TOSHIBA 
 
15 
Battery Backup Time 
The exact amount of backup time provided will vary depending on 
the UPS model being used, number of batteries, condition of the 
batteries and other factors.  However, the chart below gives the 
times that can be expected from the standard units with batteries in 
good condition.  For greater backup time, an additional battery 
module may be added to the standard unit.  Only one additional 
battery module may be added to the standard unit.  For longer 
runtime options contact your Toshiba sales representative or the 
Toshiba marketing department at (800) 231-1412 or by e-mail at 
toshibaups@tic.toshiba.com. 
Table 1 
 Backup Time* 
UPS Model 
With 1 Battery Module 
Full Load / Half Load 
With 2 Battery Modules 
Full Load / Half Load 
2000 VA 
10 min / 25 min 
25 min / 60 min 
2400 VA 
7 min / 20 min 
23 min / 50 min 
* Times given are approximate and will vary depending on the age of the batteries, the 
battery temperature, the number of previous discharges and the type of load.
 
 
Load Shed Function 
The 1700 Series includes a load shed function.  During battery 
backup operation, this function allows the load connected to two of 
the receptacles (figure 1, page 9) to be turned off in an effort to 
conserve power for more critical loads.  The battery level at which 
these two receptacles will be turned off, or “shed”, can be set by the 
user (see “The Function Control Button”, page 16).  By default, this 
feature is configured so that these two receptacles will remain on for 
the full battery backup time available (no “shedding”) 
 
Battery Recharge Time 
The following table gives estimates on time required to recharge the 
UPS’s batteries.  The recharge time may vary depending on the 
battery temperature, the age of the batteries, and other factors. 
Table 2 
Battery Recharge Time* 
Unit 
With 1 Battery Module 
With 2 Battery Modules 
2000 VA 
3 ½ hours 
7 hours 
2400 VA 
3 ½ hours 
7 hours 
* Recharge times are to 90% full capacity. 
 
Fan Speed 
The 1700 Series Rackmount UPS has variable speed fans.  The fan 
speed will vary depending on a number of factors.  As the load