Toshiba reliability in motion 1700 Manuel D’Utilisation

Page de 39
TOSHIBA 
 
19 
Fixed Frequency Mode 
The 1700 Series Rackmount UPS has the option of operating in a 
fixed frequency mode.  Normally the UPS operates in the frequency 
auto-detect mode.  If a specific output frequency is required (i.e. 
50Hz or 60Hz) the UPS can be set at the factory to supply the 
desired frequency regardless of the input frequency (input frequency 
must be within allowable limits, see Specifications on page 29).  For 
a unit already in use the output frequency can be set through 
software.  For instructions on setting the output frequency through 
software please contact Toshiba at (800) 231-1412 or by e-mail at 
toshibaups@tic.toshiba.com.  It is important to note that when the 
UPS is operating with a fixed output frequency, output is 
disabled in bypass.
 
 
Adding an Additional Battery Module 
Note:  Only one additional battery module may be added to the 
standard unit.  Figure 4 shows the standard unit with one additional 
battery module added.  To install an additional battery module follow 
these steps: 
 
1)  Make room in the rack for the additional battery module to be 
placed below the other modules.  Secure the new battery module 
in the rack. 
 
2)  Plug the new battery module output power cord into the battery 
input plug on the battery module. 
 
  
 
Figure 4 
Expansion Battery Module