Appendix D:  Parallel Operation 
The 1700 Series Rackmount UPS offers a standard feature that allows 
the unit to operate with very low input voltage without de-rating the 
output power.  If the input voltage drops below a certain point the unit will 
switch to parallel mode.  Parallel mode means that the unit is using the 
available input voltage and supplementing with battery power.  Because 
battery power is being used, the time the unit can operate in parallel 
mode is limited.  However, the time will be longer than that available 
when the unit is operating on battery power alone.  The point when the 
UPS will enter parallel mode will vary depending on the output load.  The 
following graph shows the various stages based on full output load and 
75% output load. 
 
 
 
As shown by the graph the lower the output load the lower the input 
voltage can go before parallel mode is activated.  However, the minimum 
input voltage will always remain at 50% (60VAC for a 120VAC system).