Emerson 3000 Manuel D’Utilisation

Page de 88
Installation (Applicable to all Models)
Liebert
®
 Challenger 3000
10
2.5
Piping Considerations
All piping below the elevated floor must be located so that it offers the least resistance to air flow. 
Careful planning of the piping layout under the raised floor is required to prevent the air flow from 
being blocked. When installing piping on the subfloor, it is recommended that the pipes be mounted in 
a horizontal plane rather than stacked one above the other. Whenever possible, the pipes should be 
run parallel to the air flow.
Condensate pumps for downflow units are shipped separately to be field-installed under the raised 
floor. Pump height is 11 in. (279mm).
2.5.1 Drain Line
A 3/4" (19.1mm) female pipe thread (FPT) connection is provided for the evaporator coil condensate 
drain. This drain line also drains the humidifier, if applicable. The drain line must be located so it will 
not be exposed to freezing temperatures. The drain should be at least the full size of the drain 
connection and pitched a minimum of 1/8" per ft. (11mm per meter).
NOTICE
Risk of water backing up in the evaporator coil drain line. Can cause the drain pan to 
overflow, resulting in building and equipment damage.
Do not install an external trap in the drain line of units without a condensate pump. This line 
already has a factory-installed trap inside the cabinet.
NOTICE
Risk of drain line damage. Can cause water leaks resulting in furniture, equipment and 
building damage.
This line may contain boiling water. Select appropriate drain system materials.
Units with a condensate pump will require a field-supplied trap downstream from the pump. 
The drain line must comply with all applicable national, state and local plumbing codes.
Table 2
Piping connection size
Air-Cooled Unit Connection Sizes—in.
Model No. BF/BU
(50 Hz)
Liquid Line O.D. Copper
L
Hot Gas Line OD Copper
HG 
042A (040A)
3/8
5/8 
067A (065A)
1/2
7/8 
Split System Fan Coil Unit Connection Sizes—in. 
Model No. BF/BU (50 Hz)
Liquid Line
L
Suction Line
SC
036E (035E)
5/8 - 18 Female (#6 QC) 
1-1/8 - 12 Female (#11 QC)
060E (059E)
1/2 OD Cu
1-1/8 OD Cu
All Units: Connection Sizes—in. 
Humidifier Line
OD Copper
H
Condensate
Drain Line
C
Condensate Pump Line 
OD Copper
P
Hot Water Reheat
OD Copper
1/4
3/4 FPT
1/2 
Supply 
HWS
Return 
HWR
5/8
5/8
Water/Glycol-Cooled Unit Connection Sizes—inches
Model No. BF/BU
(50 Hz)
Supply Line
S
Return Line
R
046WG (045WG)
7/8
7/8
071WG (070WG)
1-1/8
1-1/8
GLYCOOL Unit Connection Sizes —in. 
Model No. BE/BK
(50 Hz)
Supply Line
S
Return Line
R
061G (058G) 
1-1/8 
1-1/8