Emerson 3000 Manuel D’Utilisation

Page de 88
Air-Cooled Models—Self-Contained Compressor
31
Liebert
®
 Challenger 3000
Figure 16 General arrangement—Air-cooled models with digital scroll and fan speed control
DPN001726
Rev. 2
Condenser
Coil
Schrader
Valve
Schrader
Valve
Optional Field-Installed
Fusible Plug
Evaporator
Coil
Solenoid
Valve
Sight
Glass
Filter
Drier
Liquid Return
Shutoff*
Valve
External
Equalizers
Sensing
Bulb
Digital
Compressor
Digital
Solenoid Valve
Service
Valves
Hot Gas
Discharge
Check
Valve
FIELD PIPING
FACTORY PIPING
SINGLE CIRCUIT SHOWN
* Components are not supplied by Liebert but
  are recommended for proper circuit operation
  and maintenance.
Expansion
Valve
* Inverted trap on
  discharge and liquid lines
  to extend above base of
  coil by a minimum
  of 7-1/2" (190mm)
* Trap at base
  of risers longer
  than 5ft. (1.5m)
* For rises over
 25ft. (7.6m), trap
 every 20ft. (6m) or
 at evenly spaced
 points