Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor
Liebert
®
 Challenger 3000
54
5.5.4 Motor Ball Valve—Digital Scroll Compressors
valve.
5.6
Condenser
The condenser is designed to operate in conjunction with a drycooler. The maximum coolant pressure 
is 350 psig (2413 kPa).
5.7
Glycol Regulating Valve
The glycol regulating valve automatically regulates the amount of coolant necessary to remove the 
heat from the refrigeration system, permitting more fluid to flow when load conditions are high and 
less fluid to flow when load conditions are low. The valve consists of a brass body, balance spring, 
valve seat, valve disc holders, capillary tube to discharge pressure, and adjusting screw.
5.7.1 Standard Valve - 150psig (1034kPa) System for 3 & 5-Ton Units (Johnson Controls Valve)
High Pressure Valve - 350psig (2413kPa) System for 5-Ton Units (Johnson Controls Valve)
5.7.2 High Pressure Valve - 350 psig (2413 kPa) System for 3-Ton Units (Metrex Valve)
5.7.3 Testing Valve Function
When the refrigeration system has been Off for approximately 10-15 minutes, the coolant flow should 
stop.
Should the coolant continue to flow, the valve is either improperly adjusted (head pressure is too low) 
or the pressure sensing capillary is not connected properly to the condenser.
Table 20
Refrigerant control settings psi (kPa)
Low Pressure
Cut Out 
Low Pressure
Cut In 
High Pressure
Cut Out 
20 (137.9) 
65 (448.2) 
400 (2758)