Emerson 3000 Manuel D’Utilisation

Page de 88
Split System Models
Liebert
®
 Challenger 3000
74
7.6
Water and Glycol-Cooled Condensing Units
For installation guidelines, refer to Installing the Indoor Condensing Unit on page 67.
7.6.1 Piping Considerations
It is recommended that manual service shutoff valves be installed at the supply and return line to 
each unit. This will provide for routine service or emergency isolation of the unit.
When the water source for the condenser is of poor quality, it is good practice to provide cleanable 
filters in the supply line. These filters will trap the particles in the water supply and extend the 
service life of the water-cooled condenser.
3-Ton Connection Sizes
5-Ton Connection Sizes
7.6.2 Condenser Water Requirements
The standard maximum water pressure is 150 psig (1034 kPa). For applications above this pressure, 
consult the factory about high pressure systems.
The system will operate in conjunction with a cooling tower, city water, or drycooler.
7.6.3 Regulating Valve
Condenser Water Inlet
7/8" OD Cu
Condenser Water Outlet
7/8" OD Cu
Suction Line
1-1/8 - 12 male #11 quick connect 
Liquid Line:
5/8 - 18 male #6 quick connect 
Condenser Water Inlet
1-1/8" OD Cu
Condenser Water Outlet
1-1/8" OD Cu
Suction Line
1-7/16" - 16 male #12 quick connect 
Liquid Line
1-1/16" - 12 male #10 quick connect 
Table 32
Water and glycol-cooled condensing unit data
Model
Net Weight,
lb (kg)
Glycol Volume,
gal (l)
MC_44W
MC_43W
200 (91)
1.7 (6.4)
MC_69W
MC_68W
282 (128)
2.0 (7.6)