List AE:  Distribution Bus Module (P/N 509648) 
(8) GJ/218 Circuit Breaker System Positions (Lower Two Rows) 
Features 
♦  Single Voltage Distribution (+24V) 
♦  1,000A Maximum Capacity (500A per side) 
♦  (8) Load Distribution Circuit Breaker Mounting Positions 
(100 to 600A GJ/218-Type) NOTE RESTRICTIONS 
Restrictions 
Occupies two distribution rows. 
For use in a 2-, 3-, or 4-bus row cabinet.  Must be installed in bus positions A and B (rows 1 and 2), or B and 
C (rows 2 and 3).  See also 
 for similar application in bus positions C and D (rows 3 and 4). 
Panel is designed to mount circuit breakers in the following possible combinations per side
(4) 100A to 250A 
(2) 100A to 250A and (1) 300A or 400A 
(2) 300A or 400A 
(1) 600A and (1) 100A to 250A 
Unless otherwise specified circuit breakers are divided between the two sides, and are mounted from left to 
right, starting with the highest capacity and working to the lowest capacity on each side. 
Ordering Notes 
1)  Order circuit breakers and associated jumper kits as required per Tables 
2)  Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position 
per Table 
1"
LOAD CONNECTIONS
1-7/8"
1"
1"
GROUND
BUSBAR
LOAD RETURN
CONNECTIONS
LOADS
3/8-16 CAPTIVE NUT, 32 PLACES (CUSTOMER MUST PROVIDE LUG 
BOLTS AND ADDITIONAL HARDWARE.  BOLT LENGTH: 1-1/4")