Spec. No. 581126000 (Model 700
NVBA
 
Page 40 of 123 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
List AJ:  Distribution Bus Module (P/N 520819) 
(2) TPH Fuse System Positions with Load Metering Shunts 
Features 
♦  Single Voltage Distribution (+24V) 
♦  500A Maximum Capacity 
♦  (2) Distribution Fuse Mounting Positions 
(70 to 600A TPH-Type) 
♦  (1) Load Shunt (800A, 50mV) per load fuse is provided.  Extended shunt leads are 22 AWG stranded 
wire, approximately 7-10 ft. long from exit point at bottom of Distribution Cabinet.  Each shunt lead is 
equipped with a 49.9 ohm current limiting resistor.   
Restrictions 
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3-, or 4-bus row cabinet.  
Does not provide connection for load returns (see Ordering Notes). 
Ordering Notes 
1)  To terminate load returns within the distribution cabinet, order one (1) 
 for up to two (2) List AJ. 
2)  Order fuses as required pe
.  Order replacement alarm fuses (1/4A) per 
3)  Order load lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required for each distribution position 
per Table 
1"
2-1/8"
LOAD 
CONNECTIONS
LOAD 
CONNECTIONS
LOAD
2-1/8"
2-1/8"
2-1/8"
3/8-16 CAPTIVE NUT, 
6 PLACES (CUSTOMER 
MUST PROVIDE LUG BOLTS 
AND ADDITIONAL HARDWARE.
BOLT LENGTH: 1-1/4")
3/8-16 CAPTIVE NUT, 
6 PLACES (CUSTOMER 
MUST PROVIDE LUG BOLTS 
AND ADDITIONAL HARDWARE.
BOLT LENGTH: 1-1/4")
LOAD