List RA:  1200A Low Voltage Battery Disconnect (LVBD) 
Contactor and Control Circuit (P/N 540808) 
Features 
♦  Provides a battery disconnect contactor, which is mounted in bus position A (row 1) of the Distribution 
Cabinet. 
Restrictions 
Limit one bus arrangement of this type per System. 
Must be installed in bus position A (row 1) of a 1-, 2-, 3-, or 4-bus row cabinet. 
Cannot be used with List 92, 93, RB, RC, RD, or RE. 
Ordering Notes 
1)  Order as required. 
2)  Order battery lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required Tabl
1"
1-1/4"
1-1/4"
BATTERY 
(LOAD SIDE) 
CONNECTIONS
CLEARANCE HOLES FOR 3/8 BOLT, 2 PLACES 
FOR MOUNTING LUG ON BACK SIDE OF BUSBAR
(CUSTOMER MUST PROVIDE LUG BOLTS, NUTS AND 
ADDITIONAL HARDWARE.  BOLT LENGTH: 1-1/4")
3/8-16 CAPTIVE NUT, 4 PLACES 
(CUSTOMER MUST PROVIDE LUG 
BOLTS AND ADDITIONAL HARDWARE.
BOLT LENGTH: 1-1/4")