Figure 7:  Settings for Process Temperature Controller (E5CN), Part No. A0567917 
 
Mode 
Parameter 
Setting range 
Default 
Manuf. setting
Run/Stop Run/Stop Run 
Operation 
Alarm value 1 
-1999 to 9999 
25 
 
Mode 
Parameter 
Setting range 
Default 
Manuf. setting
AT execute/cancel 
ON, OFF 
OFF 
Various 
Temperature input shift 
-199.9 to 999.9 
0.0 
Proportional Band 
0.1 to 999.9 
8.0 
Various 
Integral Time 
0 to 3999 
233 
Various 
Adjustment 
Derivative Time 
0 to 3999 
40 
Various 
 
Process Air Dew Point Display 
Optional 
The Process Air Dew Point meter indicates the current process air delivery moisture content. 
Standard dryers use a microprocessor-based controller for displaying dew point air 
temperature. The controller is a modular, self-contained unit removable from the mounting 
housing. All parameters are factory set and adjusted; normally, no field adjustment to the 
internal controls are necessary. 
Figure 8:  Typical Dew Point Display Monitor – Part No. A0555757 
PV
SV
OUT1
OUT2 MANU STOP RMT
AT
SUB1
AT
E5CK
OMRON
 
Note: 
No field adjustment is required.  The dew point meter is meant for 
moisture indication only! 
Setting the High Dew Point Alarm 
The high dew point alarm setting is changed by pressing the up and down keys to input the 
alarm value. The factory setting for Alarm Value 1 
(AL-1 )
 is -10
°F (-23°C). 
Restoring the Process Air Dew Point Meter (E5CK) to Factory Setup 
If the preset parameters on the controller have been tampered with and it no longer functions 
properly, call the Service Department.  This controller is not meant to be modified.