Setting the Process Air Temperature 
When setting the process air temperature, consult with the resin manufacture for the 
recommended drying temperature. 
To change the process air temperature set point with the dryer running: 
•  Press 
 to raise the set point to the temperature you want. 
•  Press 
 to lower the set point to the temperature you want. 
Restoring the Process Air Temperature Controller (E5CN) to Factory Settings 
If the preset parameters on the controller have been tampered with and it no longer properly 
controls temperature, you can restore the controllers to the factory setup.  Call the Service 
Department for detailed instructions. 
E5CN Operating Parameters 
The E5CN controller has several mode selections. Within each mode are numerous 
parameters that can be set. 
The factory has set the security level to protect the critical parameters from being accidentally 
changed. Below is an explanation of the operating modes you will have access to and on the 
following page are the manufacturers’ default settings. 
Available E5CN Modes 
Operation Level 
Indicator 
Name 
Description 
  
Run/Stop Mode  
(r-S) 
When “RUN” is selected, the control is running.  
When “STOP” is selected, the control is stopped.  
When the control is stopped, the STOP display 
lights.  The default is set to “RUN.” 
 
Alarm Value 1 
Mode (AL-1) 
(35°F) 
This setting is used to indicate how many degrees 
the process temperature will be allowed to exceed 
the set point temperature. An alarm output will de-
energize the heaters and blower. 
 
Adjustment Level 
Indicator 
Name 
Description 
  
Auto-Tune Mode 
(At) 
See Page 19 of Chapter 3 for instructions on how 
to Auto-Tune your dryer. 
Note: 
Although the controller is calibrated at 
the factory, the manufacturer 
recommends that the unit be Auto-
Tuned prior to dryer startup. 
 
Temperature Input 
Shift Mode (TnS) 
This setting is used to offset an error between the 
set point and the actual temperature.  The entire 
input range is shifted by a set figure