tradewins-furniture rnc15 Manuel D’Utilisation

Page de 18
2
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two air streams.
It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four PVC reinforced
polyester straps that are supplied with the unit.
DEFROST
Damper defrost system; defrosts automatically as the outdoor temperature falls.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to
prevent exterior condensation. Drain connections two - 1/2" (12mm) OD.
WEIGHT
87 lbs. (39.5 kg)
SHIPPING WEIGHT
89 lbs. (40.5 kg)
CONTROLS
HRV System Control
HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by connecting
remote controls to designated terminals inside electrical box of HRV.
Standard LOW SPEED SETTING can be increased by manipulating switches in electrical box.
OFF(Standby)/LOW or OFF/HIGH speed operation also available by manipulating switches.
OPTIONAL ACCESSORIES
99-132
20 Minute Fan Timer - (3 wire) 20 gauge wire (min.) 100’ length (max.)
99-186
Weather Hoods, 2 - 6" (150mm) c/w 1/4" (6mm) screen
99-116
Dehumidistat Ventilation Control - Dehumidistat with ON/OFF
99-130
Dehumidistat Control - Dehumidistat
All units conform to CSA and UL standards.
23.5"
(597)
22.5"
(572)
26.5"
(673)
*All Duct Connections 6" (150mm) 
CONDENSATE DRAINS
DAMPER
BLOWERS
DEFROST
PORT
FRONT VIEW
TOP VIEW
SIDE VIEW
*NOTE: Front clearance 
 of 25 inches (635 mm)  
 is recommended 
 for servicing unit. 
STALE AIR
TO OUTSIDE
FRESH AIR
FROM OUTSIDE
STALE AIR
FROM INSIDE
FRESH AIR
TO INSIDE
TW-03
0204
Warranty
Two year parts.
Fifteen year aluminum core.
Performance
Net supply air flow in cfm (L/s) against external static pressure
E.S.P 
RNC15
(external static pressure)
[cfm (L/s)]
@ 0.1" (25 Pa)
177 (83)
@ 0.2" (50 Pa)
164 (77)
@ 0.3" (75 Pa)
156 (73)
@ 0.4" (100 Pa)
143 (67)
@ 0.5" (125 Pa)
123 (58)
Max.Sensible Effectiveness
78%
-13°F (-25°C) outdoor air
72°F (22°C) 40% RH indoor air
Test Parameters
67cfm (32L/s)
Sensible Effectiveness 32°F (0°C)
76%
*Sensible Efficiency 32°F (0°C)
66%
*Sensible Efficiency -13°F (-25°C)
60%
**Latent Efficiency 95°F (35°C)
0%
Total Efficiency 95°F (35°C)
20%
VAC @ 60HZ
120
WATTS / High@.3” W.C.
173
WATTS / Low @.3” W.C.
63
Engineering Data - HRV
RNC15
Dimensions RNC15
inches (mm)
TM
HEAT RECOVERY VENTILATOR
HEAT RECOVERY VENTILATOR
*Sensible Efficiency - thermal **Latent Efficiency - moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency - includes parasitic losses from fan and defrosting