RDVN Series Direct Vent Gas Fireplace
20007628
How to Use the Vent Graph
The vent chart should be read in conjunction with the 
following vent installation instructions to determine the 
relationship of the vertical and horizontal dimensions of 
the vent system.
1.  Determine the height of the center of the horizontal 
vent pipe exiting through the outer wall.  Using this 
dimension on the Sidewall Vent Graph (Fig. 12), 
locate the point intersecting with the slanted graph 
line. 
2.  From the point of this intersection, draw a vertical 
line to the bottom of the graph.
3.  Select the indicated dimension, and position the 
fireplace in accordance with same. 
Example A:
If the vertical dimension from the floor of the fireplace 
is 11’ (3.4 m) the horizontal run to the face of the outer 
wall must not exceed 14’ (4.3 m).
Example B:
If the vertical dimension from the floor of the unit is 7’ 
(2.14 m), the horizontal run to the face of the outer wall 
must not exceed 8¹⁄₂’ (2.6 m).
Twist Lock Pipes
When using CFM Corporation twist-lock pipe it is not 
necessary to use sealant on the joints. The only areas 
of the venting system that need to be  sealed with high 
temperature silicone sealant are the collars on the 
fireplace and termination, and the sliding joint of any 
telescopic vent section used in the system.
To join the twist lock pipes together, simply align the 
beads of the male end with the grooves of the female 
end, then while bringing the ends together, twist the 
pipe until the flange on the female end contacts the 
external flange on the male end. It is recommended that 
you secure the joints with three (3) sheet metal screws, 
however this is not mandatory with twist lock pipe.
To make it easier to assemble the joints we suggest 
putting a lubricant (Vaseline or similar) on the male end 
of the twist lock pipe prior to assembly.
TWL100
Twist Lock Pipe
3/12/99   djt
Male End
Female End
Screw Holes
TWL100
Fig. 11  Twist-lock pipe joints.
When installed as a rear vent unit this appliance may be 
vented directly to a termination located on the rear wall 
behind the appliance.
• 
Only CFM Corporation venting components are 
approved to be used in these applications (See 
‘Venting Components’ listed for different installation 
requirements).
• 
The maximum horizontal distance between the rear 
of the appliance (or end of the transition elbow in a 
corner application) and the outside face of the rear 
wall is 20” (508 mm). (Fig. 13, 14)
• 
Only one 45° elbow is allowed in these installations.
• 
Minimum clearances between vent pipe and com-
bustible materials are as follows:
 
Top - 2” (51 mm)
 
Sides - 1” (25 mm)
 
Bottom - 1” (25 mm)
Rear Wall Vent Application
Horizontal dimension from the outside face of the wall to 
the center of the fireplace vent flange  
   
Sidewall vent graph showing the relationship between vertical        
and horizontal dimensions for a Direct Vent flue system.
V
ertical  dimension from the fl
oor of the fireplace to 
the center of the horizontal vent pipe
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
3    4    5  6    7   8    9  10  11 12  13 14  15 16  17 18  19  20
eg:  A
eg:  B
CFM102 
DV Graphic
9/28/00   sta
Fig. 12  Sidewall venting graph. (Dimensions in feet)