kb-electronics kbsi-240d Manuel D’Utilisation
Notes:
1.
To achieve full specifications input voltage must be within ± 10% of nominal.
2.
Floating (non-grounded) or grounded input signal may be used.
3.
To change from 4 - 20mA to 1 - 5mA remove R3. To convert to 10 - 50mA add a 150Ω 1W resistor across
terminals “5” and “6.” See figure 3.
terminals “5” and “6.” See figure 3.
4.
Specifications are based on an output of 10 volts.
AC Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . 115 or 208 - 230V AC, 50/60 Hz
(1)
Signal Input Voltage
(2)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 - 25, 0 - 120, 0 - 550V DC
Signal Input Current
(2)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 5, 4 - 20, 10 - 50mA
(3)
Maximum Output Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Volts
Maximum Output Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10mA
Range of “MIN” Trimpot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 3 Volts
Range of “MAX” Trimpot . . . . . . . . . . 0 to 2 times the input voltage with maximum of 10 Volts
Linearity
(4)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 0.1%
Temperature Drift
(4)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 mV per ºC
Temperature Operating Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 - 50 ºC
4
TABLE 1 – GENERAL PERFORMANCE SPECIFICATIONS