Omron Ethernet DAServer Ver 1.x User Manual Rev 1.4                                                                 17014m14  
changed in the following sequence: DM0, 500R, DM1, 502R, DM2, ... then DAServer 
creates a separate write message for each new write value. 
 
If Any Msg Multiple Write option is checked, DAServer tries to include the new write 
value into any of previously created messages ignoring the sequence of data changing 
in the client application.  
Important! With this option maximum writing speed is achieved, but this option is not 
recommended
 if data changing sequence is important for PLC program! 
 
To delete device groups 
Deleting a device group from the list can be performed as follows: 
1. Right-click on the device group to be deleted. 
2. Select the Delete command from the shortcut menu. 
 
Note: 
When you select another part of the Omron Ethernet DAServer tree hierarchy, you 
are prompted to save the modifications to the configuration set. 
 
To configure default update intervals 
1. To configure a default update interval for the object, right-click in the Device Groups 
box. 
2. Select Config Default Update Interval from the shortcut menu. 
 
To edit update intervals 
• 
To edit the update interval for an object, double-click its value in the Update Interval 
column and make the edit. 
• Update Interval is the frequency (in milliseconds) that the DAServer acquires data from 
the topics associated with that device group. 
• Different topics can be polled at different rates in a PLC by defining multiple device-
group names for the same PLC and setting a different Update Interval for each device 
group. 
 
Note: 
When you select another part of the Omron Ethernet DAServer tree hierarchy, you 
are prompted to save the modifications to the configuration set. 
 
 
Scan-Based Message Handling 
DAServers are based on the concept of polling a hardware device for information. This 
polling is driven by a need which is expressed in the form of requests from one or more 
clients. Once a particular piece of information has been requested by a client, the 
DAServer formulates its own request and sends that request to the hardware device. The 
DAServer then waits for a response to its request. Once the information has been 
received, the DAServer passes that information back to the client, and repeats the 
process until all clients have ceased requesting information. 
 
The rate at which the DAServer will poll a particular device for a specific piece of 
information is defined in the device group (topic definition) inside the DAServer, using a 
parameter called the Update Interval. When setting this parameter, there is always a 
trade-off between the update speed of the device group and the resulting decrease in 
system responsiveness.