Omron ethernet direct dr 170 14 Manuel D’Utilisation

Page de 70
Klinkmann Automation Omron Ethernet DAServer 
44 
 
 
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.4                                                                 17014m14  
C/CPM2x PLCs 
The following table lists the supported item names for the C-series PLCs:  
 
Memory Area 
Prefix 
Tag 
Type  
Range 
Value 
Range  
Format 
Suffix 
CIO area  
(Bit status) 
IR  
Discrete  
IR0:00...IR511:15 
or 0.00...511.15 (**) 
0, 1 
 
CIO area 
(Word contents) 
 IR 
Integer 
IR0... IR511 
or 0...511 (**) 
(*) 
u s b f g l 
m d e c 
Latching Relay area  
 (Bit status) 
LR 
Discrete 
LR0:00... LR63:15  
 
0, 1 
 
Latching Relay area  
(Word contents) 
LR 
Integer 
LR0... LR63 
(*) 
u s b f g l 
m d e c 
Holding Relay area  
 (Bit status) 
HR 
Discrete 
HR0:00... HR99:15 
 
0, 1 
 
Holding Relay area  
(Word contents) 
HR 
Integer 
HR0... HR99 
(*) 
u s b f g l 
m d e c 
Auxiliary Relay area  
 (Bit status) 
AR 
Discrete 
AR0:00... AR27:15 
 
0, 1 
 
Auxiliary Relay area  
(Word contents) 
AR 
Integer 
AR0... AR27 
(*) 
u s b f g l 
m d e c 
Completion flags for 
Timers/Counters(***) 
TC 
Discrete 
TC0... TC511 
0, 1 
 
Present Values for 
Timers/Counters 
PV 
Integer 
PV0... PV511 
(*) 
u s b f g l 
m d e c 
Data Memory area 
(Bit status) 
DM 
Discrete 
DM0:0...DM9999:15 
 
0, 1 
  
Data Memory area 
(Word contents) 
DM 
Integer 
DM0... 
DM9999 
(*) 
u s b f g l 
m d e c 
 
Item/point names, corresponding to Input/Output register area CIO, may be without 
prefix.  
 
(*) Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U
("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with 
suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for 32-bit integer is 
from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999.  Default 
value range for Integer Tag Type is unsigned integer. 
 
(**) Represented memory area range is for C200HS type controller. For models C200H, 
C1000H and C2000H - accessible memory area ranges are 0:00...255:15 for Discrete 
items and 000...255 for Integer items. 
 
(***) Read only 
 