heatcraft-refrigeration-p h-im-fl1a Manuel D’Utilisation

Page de 24
9
Table 5. Equivalent Feet of Pipe Due to Valve and Fitting Friction
  Copper Tuber, O.D., Type “L” 
1/2 
5/8 
7/8  1 1/8 
1 3/8  1 5/8  2 1/8  2 5/8  3 1/8 
3 5/8  4 1/8 
5 1/8  6 1/8
  Globe Valve (Open) 
14 
16 
22 
28 
36 
42 
57 
69 
83 
99 
118 
138 
168
  Angle Valve (Open) 
12 
15 
18 
21 
28 
34 
42 
49 
57 
70 
83
  90˚ Turn Through Tee 
12 
14 
17 
20 
22 
28 
34
  Tee (Straight Through)  
  or Sweep Below 
.75 
 1.5 
2.5 
3.5 
11
  90˚ Elbow or Reducing 
  Tee (Straight Through) 
10 
12 
14 
16 
 Table 4.  Pressure Loss of Liquid Refrigerants in Liquid Line Risers  
 
  (Expressed in Pressure Drop, PSIG,  and Subcooling Loss, ˚F).
 
 
 
 
 
 
 
 
  Liquid Line Rise in Feet
 
 
 10ʼ  
 
 15ʼ  
 
 20ʼ  
 
 25ʼ  
 
 30ʼ  
 
 40ʼ  
 
 50ʼ  
 
 75ʼ  
 
 100ʼ 
 
Refrigerant  PSIG  ˚F  PSIG  ˚F  PSIG  ˚F  PSIG  ˚F  PSIG  ˚F  PSIG  ˚F  PSIG  ˚F  PSIG  ˚F  PSIG  ˚F
 
R22 
4.8 
1.6 
7.3 
2.3 
9.7 
3.1  12.1  3.8  14.5  4.7  19.4  6.2  24.2  8.0  36.3  12.1  48.4  16.5
 
R134a 
4.9 
2.0 
7.4 
2.9 
9.8 
4.1  12.3  5.2  14.7  6.3  19.7  8.8  24.6  11.0  36.8  17.0  49.1  23.7
  R507, R404A  4.1 
1.1 
6.1 
1.6 
8.2 
2.1  10.2  2.7  12.2  3.3  16.3  4.1  20.4  5.6  30.6  8.3  40.8  11.8
 
Based on 110˚F liquid temperature at bottom of riser.