f) Freeze Timer (S1 dip switch 9 & 10)
The freeze timer setting determines the maximum allowed freeze time to prevent possible
freeze-up issues. Upon termination of freeze timer, machine initiates the harvest cycle. After
2 consecutive timer terminations, machine will shut down, possibly indicating a problem.
The freeze timer is factory adjusted, and no adjustment is required.
freeze-up issues. Upon termination of freeze timer, machine initiates the harvest cycle. After
2 consecutive timer terminations, machine will shut down, possibly indicating a problem.
The freeze timer is factory adjusted, and no adjustment is required.
g) Pump-Out Pump Motor Delay (S2 dip switch 1)
The pump-out pump motor delay determines whether or not the pump motor de-energizes
for 2 seconds before restarting at the beginning of a drain cycle.
The pump-out pump motor delay is factory adjusted and no adjustment is required.
for 2 seconds before restarting at the beginning of a drain cycle.
The pump-out pump motor delay is factory adjusted and no adjustment is required.
S2 Dip Switch Setting
No. 1
Delay
(seconds)
OFF 0
ON 2
Control Board P00013-02
h) Refill Counter (S2 dip switch 2, 3, & 4) [Program Ver. 2.5 or earlier]
Do not adjust. These must be left in the factory default position or the unit will not operate
properly. The KMD-410MAH and KMD-410MWH refill 1 time.
properly. The KMD-410MAH and KMD-410MWH refill 1 time.
i) Factory Use (S2 dip switch 5) [Program Ver. 2.5 or earlier]
Must remain off.
j) Anti-Slush Control (S2 dip switch 6) [Program Ver. 2.5 or earlier]
j) Anti-Slush Control (S2 dip switch 6) [Program Ver. 2.5 or earlier]
The anti-slush control (Ver. 1.0) helps prevent slushing during the freeze cycle on small
icemakers.
It is deactivated on the KMD-410 series.
When activated, the thermistor located on the suction line checks for a 34°F (1°C)
temperature as the evaporator cools. When 34°F (1°C) is reached, a 5.9 k signal causes
the control board to de-energize the pump motor for 10 seconds.
Do not adjust. This must be left in the factory default position or the unit will not operate
properly.
icemakers.
It is deactivated on the KMD-410 series.
When activated, the thermistor located on the suction line checks for a 34°F (1°C)
temperature as the evaporator cools. When 34°F (1°C) is reached, a 5.9 k signal causes
the control board to de-energize the pump motor for 10 seconds.
Do not adjust. This must be left in the factory default position or the unit will not operate
properly.
60/60
Time
(50/60Hz)
(minutes)
80/50
100/70
120/100