V. REMOVAL AND REPLACEMENT 
 
1. SERVICE FOR REFRIGERANT LINES 
[a] SERVICE INFORMATION 
 
1) Allowable Compressor Opening Time and Prevention of Lubricant Mixture [R404A] 
The compressor must not be opened more than 15 minutes in replacement or service. Do 
not mix lubricants of different compressors even if both are charged with the same 
refrigerant, except when they use the same lubricant. 
 
2) Treatment for Refrigerant Leak [R404A] 
If a refrigerant leak occurs in the low side of an ice maker, air may be drawn in. Even if the 
low side pressure is higher than the atmospheric pressure in normal operation, a 
continuous refrigerant leak will eventually lower the low side pressure below the 
atmospheric pressure and will cause air suction. Air contains a large amount of moisture, 
and ester oil easily absorbs a lot of moisture. If an ice maker charged with R404A has 
possibly drawn in air, the drier must be replaced. Be sure to use a drier designed for 
R404A.
 
 
3) Handling of Handy Flux [R404A] 
 
Repair of the refrigerant circuit requires brazing. It is no problem to use the same handy 
flux that has been used for the current refrigerants. However, its entrance into the 
refrigerant circuit should be avoided as much as possible. 
4) Oil for Processing of Copper Tubing [R404A] 
 
When processing the copper tubing for service, wipe off oil, if any used, by using alcohol or 
the like. Do not use too much oil or let it into the tubing, as wax contained in the oil will clog 
the capillary tubing. 
5) Service Parts for R404A 
 
Some parts used for refrigerants other than R404A are similar to those for R404A. But 
never use any parts unless they are specified for R404A because their endurance against 
the refrigerant have not been evaluated. Also, for R404A, do not use any parts that have 
been used for other refrigerants. Otherwise, wax and chlorine remaining on the parts may 
adversely affect R404A. 
6) Replacement Copper Tubing [R404A] 
 
The copper tubes currently in use are suitable for R404A. But do not use them if oily inside. 
The residual oil in copper tubes should be as little as possible. (Low residual oil type 
copper tubes are used in the shipped units.)