FIELD CONTROLS 46477500 Manuel D’Utilisation

Page de 4
 
Page 2
 
I. 
MOUNTING THE CONTROL BOX (Figure 1) 
1.  Remove the kit from the packaging and inspect for 
shipping damage. 
2.  Place the pre-wired control box/thermal safety 
switch assembly on top of the water heater. 
3.  Select a location for mounting the control box, so 
that the water heater’s damper cable will reach the 
socket provided inside the control box, and the 
control box damper cable will reach the damper 
motor.  NOTE:  The pressure switch on the control 
box must be mounted vertically, see the warning on 
the pressure switch.   
WARNING: DO NOT OBSCURE ANY EXISTING 
WARNINGS OR OTHER IMPORTANT LABLES ON 
THE WATER HEATER!
 
4.  Mount the control box onto the water heater in the 
location selected, using installer-supplied sheet metal screws though the four dimpled holes in the base of the 
control box.   
WARNING: DO NOT INSTALL SCREWS INTO A RACEWAY OR OTHER ENCLOSURE CONTAINING WIRING OR 
ELECTRICALLY LIVE PARTS!
 
II. 
MOUNT THE THERMAL SAFETY SWITCHES (Figure 
2) 
1.  Select locations for the two pre-wired thermal safety 
switches on the draft hood.  The thermal safety 
switches should be mounted at right angles to each 
other, and on the side of the draft hood that is 
nearest to any potential source of depressurization 
of the structure (vent fans, oven hoods etc.). 
2.  Mark the locations of the thermal safety switches, 
and drill holes for the #10-24 mounting screws 
provided. 
3.  Mount the switches onto the draft hood using the 
screws, flat and serrated washers, and nuts 
provided.  Adjust the position of each switch such 
that the edges of the sensors are 1/8” from the edge 
of the draft hood. 
4.  Secure any excess cable with the cable clamps 
provided. 
III. 
CONNECT TO APPLIANCE CONTROL AND 
DAMPER (Figure 3) 
3.  Disconnect power to the water heater. 
4.  Remove a knockout from the control box for the 
water heater damper cable, and install the supplied 
plastic bushing into the knockout as shown. 
5.  Insert the water heater damper cable into the 
control box through the bushing, and plug it into the 
socket provided in the control box.  BE SURE TO 
ALIGN THE GROOVE IN THE PLUG WITH THE 
SPLINE IN THE SOCKET WHEN INSERTING! 
6.  Connect the control box damper cable to the 
automatic damper.  BE SURE TO ALIGN THE 
GROOVE IN THE PLUG WITH THE SPLINE IN 
THE SOCKET WHEN INSERTING! 
IV. 
INSTALL THE DI CONTROL KIT ADAPTER KIT ON THE DRAFT INDUCER (Pressure sensing port) 
1.  Refer to the included instructions with the kit for this procedure. 
 
Figure 2 
 
Figure 3 
 
Figure 1