The Crestron
 4-Feed, 4-High-Inrush Switch Terminal 
Block and Module (CLTI-4HSW4 and CLXI-4HSW4, 
respectively), are considered a single entity and must be 
used together. They ship separately to permit termination 
of the field wiring to the CLTI-4HSW4 prior to 
installation of the CLXI-4HSW4, as described in this 
guide. They can be mounted in any Crestron Automation 
Enclosure (CAEN-Series Enclosures). The terminal block 
is designed to terminate four circuit feeds (HOT and 
NEUTRAL) and distribute the controlled circuits (LOAD) 
to the fixtures. The module connects to the terminal block 
and performs switching (non-dim) control of four 
incandescent, low voltage, neon, cold cathode, 
fluorescent, or HID lighting loads, or motor loads. The 
maximum load is 8 amps (1 HP) for each controlled 
circuit (32 amps total per module). The unit requires 
230VAC 50 Hz input voltage. An oversize heat sink 
dissipates heat efficiently. There are LEDs on the module 
to indicate communication to a Cresnet
 network, input 
power to the module, and output power to the load. 
NOTE:  When connecting to an Arc Fault Breaker, 
the load should not exceed 1000 watts.  
Terminal Block & Module Locations (Double-wide Enclosure) 
Installation 
GROUNDING TERMINAL BLOCKS
MODULE
TERMINAL BLOCK
(LEFT)
TERMINAL BLOCK
(RIGHT)
 
Terminal block and module must be mounted into a 
Crestron Automation Enclosure by a licensed electrician, 
in accordance with all national and local codes.  
CAUTION:  This equipment is for indoor use only 
and needs to be air-cooled. Mount in a well-
ventilated area. The ambient temperature must be 
0
°C to 40°C (32°F to 104°F). The relative humidity 
must be 0% to 90% (non-condensing).  
Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and 
right sides) of double-wide enclosures. Modules are 
installed along the right side of single-wide enclosures 
and side-by-side in the center of double-wide enclosures. 
When installing modules and terminal blocks in a double-
wide enclosure, be sure to invert units on the right side so 
that they can be properly wired. Refer to the illustrations 
shown in the next column when considering the location 
of terminal blocks and modules within an enclosure.  
NOTE:  Modules and terminal blocks must be 
installed into the lowest available spaces and 
continue toward the top of the enclosure. 