sOlID state heat PumP cOntrOl 
trOubleshOOtInG PrOceDure
 1.  NotE: A thorough understanding of the defrost  
   cycle sequence is essential. Review that section
   
earlier in this manual prior to troubleshooting the  
   
control.  Turn on AC power supply to unit.
  2.  Turn thermostat blower switch to “fan on” – the  
   
indoor blower should start.  (If it doesn’t,  
 
   
troubleshoot indoor unit and correct problem.)
  3.  Turn thermostat blower to “auto” position.  Indoor  
   
blower should stop.  NotE: Many models have a  
   1-minute blower time delay on “off” command;
   wait for this to time-out.
  4.  Set system switch to “heat” or “cool”.  Adjust    
   
thermostat to call for heat or cool.  The indoor    
   
blower, compressor  and outdoor fan should start.
NOTE: If there was no power to 24 volt transformer,
the compressor and outdoor fan motor will
 
not start for 5 minutes.  This is because of   
 
the compressor short cycle protection. 
symptom
Description, check & Possible causes
What & how to check / repair 
Compressor will not start 
(heating or cooling)
1.  check for leD illumination.
Is there an LED illuminated on the board (flashing)?
Yes = go to Step #2; No = go to Step #3
2.  check for error codes.
Is the LED flashing a Code?
Yes = go to Step #4; No = go to Step #8
3.  check for power at board.
Is there 24 volts AC between R and C?
Yes = go to Step #13; No = go to Step #9
4.  check codes.
What code is blinking?
Code “1”, go to Step #6; Code “2”, go to Step#7; Fast Blink, go to Step #5
5.  compressor delay active.
Wait for 5 minute delay or jump board’s “speed up pins”.
Check for proper operation; if still needed, go back to Step #1.
6.  low pressure fault.
Check wiring circuit and unit pressures.
7.  high pressure fault.
Check wiring circuit and unit pressures.
8.  check for compressor input signal.
Is there 24 volts AC between Y and C?
Yes = go to Step #10; No = go to Step #11
9.  no power to board.
The unit either does not have unit voltage, the transformer is bad or the unit wiring is 
incorrect.
10.  check for compressor output signal.
Is there 24 volts AC between CC & C?
Yes = go to Step #12; No = go to Step #13
11.  no “Y” compressor input signal.
Check thermostat wiring, incorrect phase of unit (see section on Phase Monitor), and 
finally unit wiring.
12.  no “cc” compressor output signal.
Check compressor contactor for proper operation and finally check compressor.
13.  Faulty board.
Replace defrost board.
Fan outdoor motor does 
not run (cooling or heating 
except during defrost)
Heat pump control defective
Check across fan relay on heat pump control. (Com-NC)
Replace heat pump control.
Motor defective
Check for open or shorted motor winding.  Replace motor.
Motor capacitor defective
Check capacitor rating.  Check for open or shorted capacitor.  Replace capacitor.
Reversing valve does not 
energize (heating only)
Heat pump control defective
Check for 24V between RV-C and B-C.
1. Check control circuit wiring.
2. Replace heat pump control.
Reversing valve solenoid coil defective
Check for open or shorted coil.
Replace solenoid coil.
Unit will not go into defrost
(heating only)
Temperature sensor or heat pump control defective
Disconnect temperature sensor from board and jumper across “SPEEDUP” terminals 
and “SEN JMP” terminals.  This should cause the unit to go through a defrost cycle within 
one minute.
1. If unit goes through defrost cycle, replace temperature sensor.
2. If unit does not go through defrost cycle, replace heat pump control.
Unit will not come out of 
defrost (heating only)
Temperature sensor or heat pump control defective
Jumper across “SPEEDUP” terminal.
This should cause the unit to come out of defrost within one minute. 
1. If unit comes out of defrost cycle, replace temperature sensor.
2. If unit does not come out of defrost cycle,  replace heat pump control.
trOubleshOOtInG
table  4
trOubleshOOtInG
 
LED BLINK CoDES
 
BLINK 
FuNCtIoN
 
Slow 
Normal function (1.0 sec on/1.0 sec off)
 
Fast 
ASCD timer active (0.1 sec on/0.1 sec off)
 
Low pressure switch failure
 
High pressure switch failure/“Soft” Lockout
 
Defrost mode active
 
High pressure switch failure/“Hard” Lockout