L404F,T,V PRESSURETROL
®
 CONTROLLERS
7
71-2429—2
CHECKOUT
After the controller has been installed, wired and adjusted, it 
should be tested with the system in operation. First, allow the 
system to stabilize. Then, observe the operation of the 
controller while raising and lowering its setpoint. Pressure 
should increase when the setpoint is raised and decrease 
when the setpoint is lowered.
Also, check the make and break points of the controller. If they 
do not agree with a separate, accurately calibrated pressure 
gauge, a slight adjustment of the scaleplate(s) may be 
necessary.
Use accurate pressure testing equipment when checking out 
the controller. Do not rely on inexpensive gauges. The 
controllers are carefully calibrated at the factory.