For HVAC Installer Only • Installation Guide
11
Fan  does  not  run  with  ventilation  activated. 
Compressor  runs  briefly  but  cycles  on  &  off 
with humidity control turned to ON.
1.  Loose connection in fan circuit.
2.  Obstruction prevents fan rotation.
3.  Defective fan.
4.  Defective fan relay.
5.  Defective fan capacitor.
Evaporator  coil  frosted  continuously,  low  de-
humidifying capacity.
1.  Defrost thermostat loose or defective.
2.  Low refrigerant charge.
3.  Dirty air filter(s) or airflow restricted.
Unit not providing ventilation.
1.  Check control wire connections (check 
connections at fresh air damper also).
2.  Defective fresh air damper.
3.  Dirty air intake. Clean outside intake hood.
Unit removes some water, but not as much as 
expected.
1.  Air temperature and/or humidity have 
dropped.
2.  Humidity meter and or thermometer used 
are out of calibration.
3.  Unit has entered defrost cycle.
4.  Air filter dirty.
5.  Defective defrost thermostat.
6.  Low refrigerant charge.
7.  Air leak such as loose cover or ducting 
leaks.
8.  Defective compressor.
9.  Restrictive ducting.
10. Optional Condensate Pump Safety Switch 
open.
Unit Test to determine problem:
1.  Detach field control wiring connections 
from main unit.
2.  Connect the yellow and green pigtails 
from the main unit together; only the 
impeller fan should run. Disconnect the 
wires.
3.  Connect the yellow and blue pigtails from 
the main unit together; the compressor 
and impeller fan should run.
4.  If these tests work, the main unit is 
working properly. You should check the 
control panel and field control wiring for 
problems next.
5.  Remove the control panel from the 
mounting box and detach it from the 
field installed control wiring. Connect the 
blue, yellow, and green wires from the 
control panel directly to the corresponding 
colored pigtails on the main unit. 
Leave the violet, white, and red wires 
disconnected!
6.  Turn on the fan switch; the impeller fan 
should run. Turn off the fan switch.
7.  Turn on the humidity control; the 
compressor and impeller fan should run.
8.  If these tests work, the problem is most 
likely in the field control wiring.
9.2 Refrigerant Charging
If the refrigerant charge is lost due to service or a 
leak, a new charge must be accurately weighed in. 
If any of the old charge is left in the system, it must 
be  recovered  before  weighing  in  the  new  charge. 
Refer to the unit nameplate for the correct charge 
weight and refrigerant type.
9.3 Compressor/Capacitor Replacement
This  compressor  is  equipped  with  a  two  terminal 
external overload and a run capacitor, but no start 
capacitor or relay.
CAUTION-ELECTRICAL SHOCK HAZARD: 
Electrical power must be present to perform 
some tests. These tests should be performed 
by a qualified service person.