The rdcEnetFO safely and easily extends your panel 
mounted ethernet devices via fiber optic cables by 
up to 40 km long, while providing the ultimate 
combination of  isolation, surge, and noise 
protection. WDM (Wavelength Division 
Multiplexing) option reduces the amount of cabling 
by half. All ports are galvanically isolated from the 
DC supply ground.  Connectors are guaranteed to 
work with 9/125, 62.5/125, 100/140, and 50/125 
µm fiber sizes.
Isolation, industrial design, small size, DIN rail mount, 
user indication, and wide range DC supply make the 
rdcEnetFO a very engineer- friendly device for your 
industrial data communication system.
Model: rdcEnetFO
Ethernet to Multimode Fiber Optics Converter
Ethernet to Singlemode Fiber Optics Converter
Ethernet to WDM Fiber Optics Convert
er
Specification
Network Interface
Connector
Fiber Size
Optical Wavelength
Power Budget
Fiber Optic
: ST, SC, FC
: 62.5/125, 100/140, 50/125 and 9/125 um
: Multimode - 1300 nm 
: Singlemode - 1310nm
: WDM - 1310/1550 nm
: -16 dbm for Multimode
: -31.5 dbm for Singlemode
: -21 dbm for WDM
Block Diagram
ST Fiber Optics
V+
V--
Main
Supply
FO
 A
ct
screw terminals
Et
he
rne
t P
ort
RJ45 Ethernet 
Isolated
Supply
TX
RX
En
et
 A
ct
Co
nv
er
te
r
FO
  100
FO
 10
En
et
  100
En
et
  10
Interface
Connector
: 10/100Base-T Ethernet
: RJ45
Typical Application
rdcEnetFO
1
rdcEnetFO
2
Device 1
Device 2
Ethernet
Ethernet
Fiber Optic
Link Fault Pass-Through Feature
When the rdcEnetFO detects a failure at one of its links, it 
will turn off the other link as well. For example, when Device 
1 goes offline, Device 2 will be aware that a link failure has 
occured because rdcEnetFO 1 will turn off its fiber optic ports, 
thereby making rdcEnetFO 2 turn off its Ethernet port. The 
link speed indicators of both rdcEnetFOs will also be 
turned off.
Dimensions in mm (and inches)
Order Information
rdcEnetFO
Mechanical / Environment
Communication
Power Supply
Isolation
(Version 1.1) Specifications subject to change without notice.
33.8 (1.33)
78.1 (3.08)
105 (
4
.1)
110 (
4
.3)
112.5 (
4
.4)
EN 50 022 - 7.5mm
EN 50 035
EN 50 022 - 15mm
Copyright © 2007 Robust DataComm Pte Ltd
-
-
-
9v to 48v Unregulated DC Supply
Power Supply Configuration
gv
1.5 Kv isolation between Ethernet 
& power supply. Intrinsic isolation 
at fiber ports.
Galvanic Isolation Configuration
2p
Multimode - STSCFC
Singlemode - STSCFC
WDM - SC only
Supply to Enet : 1.5 KV
9 to 48 VDC : 2.16 W (90 mA @ 24 VDC, 100 Mbps).
FO Activity
Ethernet Activity
FO Link Speed
Etnernet Link Speed
Auto Negotiation
Standard Distance
: Yellow
: Yellow
: Green (100 Mbps), Yellow (10 Mbps)
: Green (100 Mbps), Yellow (10 Mbps)
: Highest possible link speed will be selected
: Ethernet - 100m with CAT 5 UTP cable
: Fiber Optics 
Operating Range
Storage Range
Relative Humidity
Case Material
Weight
Mounting Rail
: -40C to +65C
: -40 C to +100C
: 10 to 90% RH, non-condensing
: nylon polymide, fungus and termite resistant
  self-extinguishing
: approx 130g
: DIN EN 50 022 or DIN EN 50 035
www.robustdc.com
2p
gv
95 (3.74)
- 2000 m for Multimode
- 40000 m for Singlemode
- 20000 m for WDM 
Optical Technology
s
 - Singlemode
w
 - WDM
blank
 - Multimode
Connector Configuration
Co. & GST Reg. No: 19-9600 372-Z