Puls UC10.242 DIN-Rail UPS Guide De Spécification
UC10.241, UC10.242
UC-Series
24V,
15A,
C
APACITOR
-
BASED
B
UFFER
M
ODULES
13. T
ERMINALS AND
W
IRING
The terminals are IP20 finger safe constructed and suitable for field and factory wiring.
Input and output
Signals
Type
bi-stable quick-connect spring-clamp
terminals
terminals
pluggable spring-clap terminals
Solid wire
0.5-6mm
2
0.2-1.5mm
2
Stranded wire
0.5-4mm
2
0.2-1.5mm
2
American Wire Gauge
AWG 20-10
AWG 24-14
Max. wire diameter
2.8mm (including ferrules)
1.5mm (including ferrules)
Wire stripping length
10mm / 0.4inch
8mm / 0.3inch
Screwdriver -
2.5mm
slotted
Fig. 13-1 Connecting a wire
Instructions:
a) Use appropriate copper cables that are designed for
a) Use appropriate copper cables that are designed for
minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum
90°C for ambient up to 70°C minimum.
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation
regulations!
c) Ensure that all strands of a stranded wire enter the terminal
connection!
d) Unused terminal compartments should be securely
tightened or closed.
e) Ferrules are allowed.
1. Insert the wire
2. Close the lever
14/27
To disconnect wire:
reverse the procedure
Apr. 2014 / Rev. 2.0 DS-UC10.241-EN (REVC)
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany