Puls UBC10.241 DIN-Rail UPS Guide De Spécification
UBC10.241, UBC10.241-N1
U–Series
24V, 10A, DC-UPS
May. 2008 / Rev. 1.1 DS-UBC10.241-EN
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
www.pulspower.com Phone +49 89 9278 0 Germany
13/23
15. T
ERMINALS AND
W
IRING
Power terminals
Signal terminals
Type
Bi-stable, quick-connect spring-
clamp terminals. IP20 Finger-
touch-proof. Suitable for field-
and factory installation. Shipped
in open position.
clamp terminals. IP20 Finger-
touch-proof. Suitable for field-
and factory installation. Shipped
in open position.
Plug connector with screw terminal. Finger-touch-proof
construction with captive screws for 3.5mm slotted
screwdriver. Suitable for field- and factory installation.
Shipped in open position. To meet GL requirements,
unused terminal compartments should be closed.
construction with captive screws for 3.5mm slotted
screwdriver. Suitable for field- and factory installation.
Shipped in open position. To meet GL requirements,
unused terminal compartments should be closed.
Solid
wire
0.5-6mm
2
0.2-1.5mm
2
Stranded
wire
0.5-4mm
2
0.2-1.5mm
2
AWG
20-10AWG
22-14AWG
Ferrules
Allowed, but not required
Allowed, but not required
Pull-out force
10AWG:80N, 12AWG:60N,
14AWG:50N, 16AWG:40N
according to UL486E
14AWG:50N, 16AWG:40N
according to UL486E
Not applicable
Tightening torque
Not applicable
0.4Nm, 3.5lb.in
Wire stripping length
10mm / 0.4inch
6mm / 0.24inch
Fig. 15-1 Spring-clamp terminals, connecting a wire
1. Insert the wire
2. Close the lever
To disconnect wire:
reverse the procedure
Instructions:
a)
Use appropriate copper cables, that are designed
for an operating temperature of 60°C
for an operating temperature of 60°C
b)
Follow national installation codes and regulations!
c)
Ensure that all strands of a stranded wire enter the
terminal connection!
terminal connection!
d)
Up to two stranded wires with the same cross
section are permitted in one connection point
section are permitted in one connection point
16. R
ELIABILITY
Lifetime expectancy
min.
137 400h
At 10A output current, 40°C
min.
> 15 years
At 5A output current, 40°C
min.
> 15 years
At 10A output current, 25°C
MTBF SN 29500, IEC 61709
886 000h
At 10A output current, 40°C
1 482 000h
At 10A output current, 25°C
MTBF MIL HDBK 217F
397 900
At 10A output current , 40°C, ground benign GB40
545 000
At 10A output current , 25°C, ground benign GB25
The Lifetime expectancy shown in the table indicates the operating hours (service life) and is determined by the
lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours.
Lifetime expectancy is calculated according to the capacitor’s manufacturer specification. The prediction model allows
a calculation of up to 15 years from date of shipment.
lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours.
Lifetime expectancy is calculated according to the capacitor’s manufacturer specification. The prediction model allows
a calculation of up to 15 years from date of shipment.
MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures and indicates
reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily
represent the life of a product.
reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily
represent the life of a product.
All values except battery.