Weed Instrument 2C20 Interface Module Guide De Spécification

Page de 4
Weed Instrument Fiber Optics
3
EOTec 2000 Expandable ControlNet Fiber/Coax Communications Modules
2C20 Electrical Interface
Module (EIM)
Cabling and Operation
ControlNet Specifications
/Requirements Apply
Maximum nodes
48 (using coax cable length of 250m)
Maximum coax cable length
1000m (when connected to only 1 node)
Trunk connection
Anywhere on the trunk via ControlNet Tap
with 1m drop cable required
Coax cable connection
BNC
Data rate
5M baud
Propagation delay
1µs maximum per modem pair
Fiber propagation delay
5µs/km 
1.5µs/1000ft
Power indicator
Green LED illuminates with power applied
Com indicator
Green LED illuminates with data from the
coax cable input
Environmental
DIN rail mounting
Power input
Nominal 9 VDC via Interconnection Bus
Input power, maximum 
1.8 W
Operating temperature range 
-40 to +85 °C
Storage temperature range
-40 to +85 °C
Humidity (non-condensing)
5 to 95% RH
Technical Specifications:
EMC immunity 
IEC61326-1:1998
Hazardous locations 
UL/cUL and FM; Class I, Division 2,
Groups A, B, C, D, T4
Packaging (polyamide)
UL 94V-0
Optical Interface Modules (OIM)
Optical Wavelength
See table following
Communications Data Range
9.6K to 12 Mbps
Optical Port Connection
ST Compatible
Optical Dynamic Range
See table following
Optical Transmit Indicator
Green LED
Optical Receive Indicator
Amber LED
Environmental
DIN rail mounting
Power input
Nominal 9 VDC via Interconnection Bus
Operating temperature range 
-40 to +85 °C
Storage temperature range
-40 to +85 °C
Humidity (non-condensing)
5 to 95% RH
EMC immunity 
IEC61326-1:1998
Hazardous locations 
UL/cUL and FM; Class I, Division 2,
Groups A, B, C, D, T4
Packaging (polyamide)
UL 94V-0
Power Supply Modules
(PSM)
Power Requirements:
Input Voltage
90-260 VAC 50/60 Hz and
120-260 VDC (2A06/2A16)
15-30 VDC (2A08/2A18)
Input Current
250 mA (2A06/2A16)
400 mA (2A08/2A18)
Input Fuse
400 mA Slow-Blow
Nominal Output
9 VDC, 1.1A Max.
to backplane connector
Alarm Relay
Form C, 175 VDC, 1A Continuous
(2A16 and 2A18 only)
Indicators
Power On (Green LED)
Environmental and Safety:
DIN rail mounting
Operating temperature range
-40 to +85 °C
Storage temperature range
-40 to +85 °C
Humidity (non-condensing)
5 to 95% RH
Electrical Safety
UL Recognized (2A06/2A16 only)
CE Approved
Hazardous locations (2A08/2A18
only)
UL/cUL and FM; Class I, Division 2,
Groups A, B, C, D, T4
Packaging (polyamide)
UL 94V-0
OIM
Fiber 
Max Optical Dynamic
Typical Max 
Model
Wavelength
Fiber Type
Connector
Range, Fiber Size
Distance
2E07, 2D07
850nm
Multimode
ST*
12dB, 62.5/125µm
2mi/3.4km
2E09, 2D09
1300nm
Multimode
ST*
12dB, 62.5/125µm
5mi/8km
2E10, 2D10
850nm
Multimode
ST*
17dB, 62.5/125µm
3mi/4.8km
2E19, 2D19
850nm
Multimode
ST*
17dB, 62.5/125 µm
7mi/11.3km
2E36, 2D36
1300nm
Single-mode
ST*
10dB, 9/125µm
12mi/20km
2E46, 2D46
1300nm
Single-mode
ST*
16db, 9/125µm
12mi/20km*
Optical Interface Modules (OIM)