Weed Instrument MXRS-2 Bi-Directional Module Guide De Spécification

Page de 2
Safety and Warning Information 
POWER:  The  MXRS  obtains power from the 10+2 
interconnection bus.  Power originates from an MX 
Base Module (see specification section). 
SERIAL DATA:  The  Port-1  I/O  terminal block is at 
the top-front of the unit. Port-2 is directly below it. On 
a 4 port model, Port-3 is at the bottom-front of the unit 
with  Port-4 directly below and behind it.   Screw 
terminal  blocks are numbered from left-to-right as 
follows: 
 
Important Notice - Before utilizing the product, the user should 
determine the suitability of the product for its intended use.  The 
user assumes all risk and liability in connection with such use.  
ULTRA ELECTRONICS’  WRITTEN WARRANTY FOR THE 
PRODUCT IS MADE IN LIEU OF ALL OTHER WARRANTIES, 
EXPRESSED OR IMPLIED WARRANTIES OF 
MERCHANTABILITY AND FITNESS FOR A PARTICULAR 
PURPOSE.  The user's exclusive remedy for breach of Ultra 
Electronics' written warranty shall be the repair or replacement 
of such quantity of product which is proven to be defective.  In 
no case shall Ultra Electronics be liable for any special, 
incidental, or consequential damages based upon breach of 
contract, negligence, strict liability or other legal theory. 
 
Approval Agency Controlled Document 
No changes authorized without prior agency approval 
Publication Number: 
           RM0900203  Rev. 0 
 
MX Multiplexer RS-232 or RS-485 
Serial Communications Module 
 
For use ONLY with the  
EOTec MX Multiplexer Line 
 
Connections 
 
Nuclear Sensors & 
Process Instrumentation 
  EOTec MX Multiplexer Models 
MXRS-2 / MXRS-4 
MX RS-232/485 Modules 
Installation Instructions 
Original Instructions 
 
 
Regulatory Information 
INDUSTRIAL CONTROL EQUIP. FOR HAZ. LOC. 
CLASS I, DIVISION 2, GROUPS A,B,C, & D, T4 
Do not disconnect equipment unless area is known to 
be non-hazardous. Certified components for use in a 
suitable enclosure.  Substitution of components or 
other equipment  modification may impair suitability. 
Ambient Temperature:  -40 .. 85C Max 
Electrical Rating:  24Vdc, 100mA 
 
                  
                  
 
FM11ATEX0067X 
II 3 G Ex nA IIC T4 Ta = -40 ºC to 85 ºC 
 
Connect the DIN Rail, via the Model 
2A09 End Clamp, to Protective Earth 
(PE) ground with low impedance. 
ATEX Specific Conditions of Use 
Modules shall be installed in an enclosure which 
maintains an ingress protection rating of IP54 and 
meets the enclosure requirements of EN60079-0 and 
EN60079-15.  The EOTec modules shall be installed 
in DIN rail with DIN end clamps mounted on both 
sides of the module set.  The DIN rail must be 
connected to Protective Earth in order to provide 
modules with a Protective Earth connection.  Do not 
disconnect equipment connections or modules when 
energized. 
 
 
Ultra Electronics 
N
UCLEAR SENSORS & PROCESS INSTRUMENATION 
707 Jeffery Way, PO Box 300 
Round Rock, TX 78680-300 USA 
Toll Free:   800-880-9333            
Telephone:  +1 512-434-2850 
Fax:  +1 512-434-2901 
Email:  fiberop@ultra-nspi.com 
www.ultra-nspi.com 
Ultra Electronics, Nuclear sensors & Process 
Instrumentation is a business name of Weed Instrument 
Co., Inc