Puls ML30.241 Power Supply Guide De Spécification

Page de 22
 
 
ML30.241
 
 
MiniLine 
 
24V,
 
1.3A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
11.  T
ERMINALS AND 
W
IRING
 
All terminals are easy to access when the power supply is mounted on the panel. Input and output terminals are 
separated from each other (input below, output above) to help in error-free wiring. 
 
 
Input Output 
 
Type 
screw terminals 
screw terminals 
 
Solid wire 
0.5-6mm
2
 0.5-6mm
2
 
 
Stranded wire 
0.5-4mm
2
 0.5-4mm
2
 
 
American Wire Gauge 
20-10 AWG 
20-10 AWG 
 
Wire stripping length 
7mm / 0.275inch 
7mm / 0.275inch 
 
Screwdriver 
3.5mm slotted or 
Pozidrive No 2 
3.5mm slotted or 
Pozidrive No 2 
 
Recommended tightening torque 
1Nm, 9lb.in 
1Nm, 9lb.in 
 
Instructions: 
a)  Use appropriate copper cables that are designed for an operating temperature of:  
60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum.  
b)  Follow national installation codes and installation regulations! 
c)  Ensure that all strands of a stranded wire enter the terminal connection!  
d)  Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire). 
e)  Do not use the unit without PE connection. 
f)  Screws of unused terminal compartments should be securely tightened. 
g)  Ferrules are allowed. 
 
 
 
12.  R
ELIABILITY
 
These units are extremely reliable and use only the highest quality materials. The number of critical components such 
as electrolytic capacitors has been reduced. 
 
 
AC 100V 
AC 120V 
AC 230V 
 
Lifetime expectancy 
*)
 
151 000h *) 
171 000h *)  174 000h *) 
at 24V, 1.3A and 40°C 
 
259 000h *) 
259 000h *)  254 000h *) 
at 24V, 0.65A and 40°C 
 
386 000h *) 
426 000h *)  484 000h *) 
at 24V, 1.3A and 25°C 
MTBF 
**)
 SN 29500, IEC 61709 
2 123 000h 
2 312 000h 
2 405 000h 
at 24V, 1.3A and 40°C 
 
3 688 000h 
3 971 000h 
4 124 000h 
at 24V, 1.3A and 25°C 
MTBF 
**)
 MIL HDBK 217F 
1 219 000h 
1 270 000h 
1 187 000h 
at 24V, 1.3A , 40°C; Ground Benign GB40 
 
1 611 000h 
1 686 000h 
1 588 000h 
at 24V, 1.3A , 25°C; Ground Benign GB25 
 
295 000h 
314 000h 
309 000h 
at 24V, 1.3A , 40°C; Ground Fixed GF40 
 
380 000h 
405 000h 
400 000h 
at 24V, 1.3A , 25°C; Ground Fixed GF25 
*)   The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime 
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the 
capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years 
(131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices. 
**)  MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a 
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. 
 
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that 
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit 
has been running for 50 000h or only for 100h. 
xxx. 201x / Rev. 1.0  DS-ML30.241-EN 
All parameters are specified at 24V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
10/22