Puls ML30.241 Power Supply Guide De Spécification

Page de 22
 
 
ML30.241
 
 
MiniLine 
 
24V,
 
1.3A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
2
40V 
+10%
 max.
Fuse
L2
L1
L3
L
N
PE
Power Supply
AC
DC
internal
fuse
23.9.  O
PERATION ON 
T
WO 
P
HASES
 
The power supply can also be used on two-phases of a three-phase-system. A 
phase-to-phase connection is allowed as long as the supplying voltage is 
below 240V
+10%
. Use a fuse or a circuit breaker to protect the N input. The N 
input is not internally protected and is in this case connected to a hot wire. 
Appropriate fuses or circuit breakers are specified in section 23.4. 
 
23.10. U
SE 
W
ITHOUT 
PE
 ON THE 
I
NPUT
 
From a safety standpoint, the unit is internally designed according to the requirements for Protection Class 1 and 2. 
Please contact PULS if you do not plan to use the PE terminal. A different marking of the front foil is then required.  
Grounding of the input is beneficial for a high EMI immunity: Symmetrical spikes or fast transients on the input side 
can be conducted directly to earth by the built-in filter capacitors. The magnitude of such spikes or fast transients on 
the output side caused by the input is much smaller compared to not connecting this terminal to ground. 
 
 
Fig. 23-3   Earthed input 
 
Fig. 23-4   Not earthed input 
 
Surge
Y
X
L
N
Ground
Power Supply
+
-
 
 
Surge
X
L
N
Power Supply
+
-
24V
Spike
 
xxx. 201x / Rev. 1.0  DS-ML30.241-EN 
All parameters are specified at 24V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 