Puls CS10.481 Power Supply Guide De Spécification

Page de 20
 
 
 
CS10.481 
 
  CSeries 
48V, 5A, S
INGLE 
P
HASE 
I
NPUT
 
 
 
Nov. 2006 / Rev.1.1 DS-CS10.481-EN 
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
10/20 
 
  EMC Emission 
EN 61000-6-4  
Generic standards 
  Conducted emission  
EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 
Class B, input lines 
   
EN 55022 
Class A, output lines  
  Radiated emission 
EN 55011, EN 55022 
Class B 
  Harmonic input current 
EN 61000-3-2  
not fulfilled 
  Voltage fluctuations, flicker EN 
61000-3-3 
 
fulfilled 
 
This device complies with FCC Part 15 rules.  
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this 
device must accept any interference received, including interference that may cause undesired operation. 
 
The power supply does not fulfill the harmonic current standard EN61000-3-2.  
Please note: 
A power supply has to comply with EN 61000-3-2 (Standard for harmonic input current) when: 
1) the end-device is used within the European Union and 
2) the end-device is connected to a public mains supply with a nominal voltage 
≥ 220Vac and  
3) the power supply is: 
   - fitted in an end-device with an average input power in excess of 75W or  
   - fitted in an end-device with a continuous input power in excess of 75W or 
   - part of a lighting system. 
 
Exceptions:
 
End-devices for professional applications with an input power > 1000W do not need to fulfill EN 61000-3-2. 
 
Comments: 
- The average input power must be determined in accordance with EN 61000-3-2. 
- Industrial mains supplies with their own transformer are considered to be “non-public”. 
- Where individual self-contained items of equipment are installed in a rack or case 
  (e.g. devices connected in parallel), they are regarded as being individually connected to the 
  mains supply. The rack or case need not be tested as a whole. Alternatively it is also permitted 
  to assess the whole rack or case. This is recommended for devices used in professional  
  applications with an input power greater than 1000W.