CyberPower RMCARD202 Manuel D’Utilisation

Page de 81
 
 
 PowerPanel™ Business Edition 
 
 
 
 
 
 
 
 
 
 
 
       25    
Configuration 
The UPS/Configuration page allows for customized UPS configurations to meet specific operational 
requirements.  
 
UPS/Configuration page 
Supplied Power 
z  Voltage: Sets the output voltage which is supplied to the connected equipment.  
Note: On some models belong to  Paragon Tower series, this setting becomes configurable in bypass 
mode and the changes require a restart to activate. 
 
z  Frequency Working Mode: Smart App Online series support two frequency modes: Follow-
up and Fixed. In Follow-up mode, the UPS supplies power in reference to the utility frequency. Once 
utility frequency varies and is out of tolerance, the UPS supplies power with a fixed frequency to avoid 
supplying the connected equipment power at an improper frequency. The fixed frequency depends on  
the utility frequency as the UPS is starting.  
In Fixed mode, the UPS supplies power at a fixed frequency without following utility frequency.  When 
the input frequency is unstable, such as power supplied by generators, set UPS to fixed mode to supply 
power with a stable frequency.  
The UPS can be set to fixed mode to use this fixed frequency to supply power to the connected