 PowerPanel™ Business Edition 
 
 
 
 
 
 
 
 
 
 
 
       73    
Technical Support
 
Troubleshooting 
1.  I cannot access the PowerPanel
®
 Business Edition web interface after complete installation. 
Please follow the below steps resolve the problem: 
z  Make sure that there is no other application utilizing port 3052 (UDP/TCP) and port 8443 (TCP). Use 
a command prompt with the command “netstat -o” to obtain information about which ports are used 
by which programs. 
z Ensure 
the 
PowerPanel
®
 Business Edition service is running on the hosted computer. If the 
service is stopped, restart the service and then try again in the same way. 
z  Make sure the port 3052 (UDP/TCP) and port 8443 (TCP) on the hosted computer are not blocked 
by a firewall. 
z  Make sure the URL in the address filed of the browser for a remote computer is correct. 
2.  I have installed the PowerPanel
®
 Business Edition Agent on my computer, but the Agent cannot 
establish communication with the UPS. 
z  Make sure that no other application is using the serial port if the UPS is connected with a serial 
cable. 
Make sure the serial or USB cable is securely and properly connected to the UPS and computer.
 
3.  The Client cannot establish communication with the UPS/PDU. 
The lack of communication may be caused by the following conditions: 
z  The network communication between the Client computer and the UPS/PDU is down. 
z  The device network address is configured improperly. 
z  The authentication settings are configured improperly. 
Follow the steps below to resolve the problem: 
z  Verify the device network address is correct. 
z  Verify the network configuration in the device is correct. Use the Power Device Network Utility tool 
to configure the device network configuration. 
z  Verify the settings on the Security/Authentication page are correct and match the settings of the 
z  Check the network status of the UPS/PDU and Clients. 
Verify firewall settings. Port 3052(UDP/TCP), port 8443(TCP), port 162(UDP) and port 53566(UDP) 
should be unblocked. The Client communicates with UPS/PDU and Agents using these ports.
 
4.  Troubleshooting when I failed a battery test?