Description 
 
The DataCollector Unit is the central system control/data collection unit for 
a Smart Route AMR network. The Network is designed to automatically 
and remotely gather readings from a number of Water Meters located 
within a defined area. 
 
Note Please refer to the Technical Manual for further information. 
 
Specification 
 
Power Supply:  
12-18Vdc 800mA 
Operating Frequency:  
902MHz to 928MHz (Frequency Hopping) 
GPRS Modem 
Quad Band PTRCB, FCC approved 
 
Required Equipment 
 
The following items are required for DataCollector installation: 
• 
DataCollector Unit. 
• 
12-18Vdc 800mA Power supply. 
• 
ISM band Antenna (part no 63000402) 
• 
GPRS Antenna (part no 63000403) 
• 
USB-A to USB-miniB Cable. 
• 
Computer running Windows XP
 
/ Vista / 7. 
• 
‘DataCollector USB Configurator’ software. 
• 
DataCollector Commissioning software 
 
 
Installation Instructions 
 
Important: SmartRoute Systems are intended to be professionally 
installed. Only a half-wave dipole antenna with a maximum gain of 
2.2dBi must be used as the ISM band antenna with this product to 
meet the FCC regulations. No other antenna apart from the part 
specified above must be used as the GPRS antenna. 
 
The unit is designed to be wall-mounted or pole-mounted in normal 
operation. 
 
To mount the unit: 
1. 
Remove the power-connector-side end-panel by undoing the 4 
screws and slide the PCA outside. 
2. 
Insert the simcard into the simcard holder. The configuration process 
for the GPRS network settings are detailed within the Configuration 
Software Manual. 
 Close the end-panel by fixing the screws back. 
3. 
Connect a suitable 18Vdc Power Supply to the DC IN port and check 
if the Power LED turns ON indicating the unit is  powered up. 
4. 
Connect a USBminiB to USB-A cable on a laptop running the 
configurator software and program the GPRS settings into the unit. 
Refer to the configuration procedure document for details. Disconnect 
the USB lead once the configuration is done. 
5. 
Fix the unit to a wall or pole atleast 3m above the ground. 
6. 
Before fixing, ensure the Box is positioned so that the antennas are 
orientated vertically (upwards). 
7. 
Then follow the instructions in the Network Commissioning section 
below. 
 
Network Commissioning Procedure 
 
Connect to the unit via the GPRS network using the DataCollector 
Commissioning software on the laptop. 
 
Once a connection has been established, the program will read the 
existing configuration from the DataCollector. A message will be displayed 
indicating if the configuration data has been successfully received. 
The DataCollector may now be configured, as follows: 
1. 
Choose a unique ‘Network ID’. i.e. an ID that is not already used by 
an adjacent SmartRoute Network. This value must be different from 
the Default of 255.  
2. 
Enable the Level-1 Commissioning Mode on the DataCollector before 
installing any endpoints on the site. Wait until all the endpoints on the 
site are installed or until the end of day whichever is earlier. Load a 
list of installed endpoints into the Commissioning software and using 
the Network Check function verify if all the endpoints have been 
picked up by the DataCollector.  
3. 
If not, then enable the Level-2 Commissioning Mode on the 
DataCollector and wait for it to complete. If all endpoints are still not 
picked up, enable the Level-3 commissioning mode and so on until 
Level-7. 
4. 
Once all the endpoints for the installation site are installed, initiate the 
Auto network formation to re-establish the network with optimum links 
to get the best coverage with reliable links. 
 
See the ‘Network Commissioning Manual’ for more details on the available 
settings. 
 
General Warnings and Safety 
 
Caution Ensure a separation distance of at least 20 cm (8 inches) is 
normally maintained between the transmitter’s antenna and the body of 
the user or nearby persons. The DataCollector is not designed for or 
intended to be used in portable applications within 20 cm. (8 inches) of the 
body of the user. 
Warning Changes or modifications to the product not expressly approved 
by BluTower could void the user’s authority to operate the equipment. See 
FCC information below. 
 
This sheet provides instructions needed to successfully connect and 
configure the DataCollector for use in a SmartRoute Network. These 
instructions are only a supplement to training in the operation of the 
product. For further training information, contact BluTower directly. 
 
Regulatory Information 
 
FCC Part 15 Regulation 
This device complies with Part 15 of the FCC Rules. Operation is subject 
to the following two conditions: 
(1) this device may not cause harmful interference, and 
(2) this device must accept any interference received, including 
interference that may cause undesired operation. 
 
It is the users responsibility to ensure that the instructions below are 
strictly followed and any non-compliance could void the user’s authority to 
use this device.  
i) The antenna used on this equipment must provide a minimum 
separation distance of 20cm from all persons. 
ii) This device should not transmit simultaneously with any other antenna 
or transmitter except as approved by FCC under this filing. 
iii) Use of any amplifiers or signal boosters with this product is strictly 
prohibited. 
 
 