S610S Manual  - Hardware Installer Manual  - Version 1.8 
36 
 
Typical wiring for two turnstiles 
Above, typical wiring for two turnstiles/speed-gates or one bidirectional unit with two restrictors 
fitted. 
Controlling power to a turnstile 
 
Sample wiring for a uni-directional turnstile barrier with external PSU. 
NOTE: S610E and S610S reader dry contact relay outputs support up to 24V. 
Unless set otherwise the default relay states on a reader are Fail Safe. 
• 
When power fails to a reader the Normally Open position becomes in a Closed state. 
• 
If the reader output is configured to operate in Fail Secure mode, power failure to the reader 
will result in Normally Open remaining in the Open position. 
• 
An installer should always check Relays states using a multi-meter. 
 
Wiring a bidirectional turnstile 
                
 
 
 
 
S610E/S610S Inputs and Outputs 
S610S or S600E master reader Inputs and outputs in Turnstile modes 
IP0  
Input  
Used to record Turnstile position after Readhead0 cardswipe  
Shows an S610E or S610S Master and Exit reader 
connected to a sample bi-directional turnstile. 
Request to Exit buttons can also be connected to J6 inputs 
IP2 and IP3  if required   
 
Shows an S610E or S610S Master reader connected to a 
sample bi-directional turnstile. 
Request to Exit buttons can also be connected to J6 inputs 
IP2 and IP3  if required