Inovonics Wireless Corporation 3B6OT9ESL Manuel D’Utilisation

Page de 3
© Inovonics, 2009 - www.inovonics.com
EN1242 EchoStream
®
 Smoke Detector 
Transmitter
Installation Instructions - 05362F
1 Overview
The EN1242 smoke detector is a wireless, battery powered photoelectric 
smoke sensor. The sensor includes a built-in sounder for alarm alerts, a 
visual status LED, and an Inovonics Wireless EchoStream transmitter. The 
sensor works as part of a security/fire alarm system and communicates 
with the system control panel. Under normal (non-alarm) conditions, the 
LED flashes once every eight seconds while the sensor monitors the 
surrounding conditions. When the sensor detects smoke, the LED lights, 
the built-in sounder beeps loudly, and an alarm signal is transmitted. The 
smoke sensor is powered by the two included three-volt lithium batteries. 
When the EN1242 detects an inactive smoke sensor a tamper message 
will be transmitted.
Note: For UL installations, refer to the EN4216R Installation and Operation 
Manual or the EN7285 Installation Instructions.
1.1 Inovonics Wireless Contact Information
If you have any problems with this procedure, contact Inovonics Wireless 
technical services:
• E-mail: support@inovonics.com
• Phone: (800) 782-2709; (303) 939-9336
1.2 EN1242 Components
 Figure 1  EN1242 Components
1.3 EN1242 Features
 Figure 2  EN1242 Features
2 Installation and Startup
2.1 Install Batteries
1. Turn the sensor housing counterclockwise 15 degrees and detach it 
from the mounting base.
2. Remove the battery compartment cover.
 Figure 3  EN1242 Battery Compartment Cover
3. Install/replace the two three-volt batteries. 
Note: A tamper message will transmit for approximately ten seconds while 
the unit powers up after the installation of both batteries. If only one battery 
is installed, the tamper message will transmit continuously.
2.2 Open the Housing
1. Using a small screwdriver to press the sensor cap release tab, apply 
downward pressure and turn the cap about one inch counter-clockwise 
to remove the cap..
 Figure 4  Remove the Sensor Cap
2. Place both thumbs on either side of the optical chamber and push down 
to detach the sensor housing.
 Figure 5  Push Down on the Optical Chamber
2.3 Select the Frequency Band
EchoStream products are able to use a range of radio frequencies, and 
must be configured for your geographic area. To configure the transmitter:
1. Place a selection jumper on the appropriate frequency band selection 
pins.
• Place the jumper on the left two pins, marked AU, to set the frequency 
range to 915-928 MHz for Australia.
• Place the jumper on the right two pins, marked NZ, to set the 
frequency range to 921-928 MHz for New Zealand.
• Leave the jumper off the pins to set the frequency range to 902-928 
MHz for North America.
2. Press the Reset button to complete configuration.
Caution: When pressing the Reset button, make sure you don’t also touch 
the frequency band selection pins. Touching the frequency band selection 
pins while pressing the Reset button can inadvertently set the device to the 
wrong frequency band.
Low Battery/Clean Me 
Selection Pins
 Frequency Band 
Selection Pins
Reset Button
Sounder Vent LED
Test/Silence 
Button
A
B
C
A
C
B
Battery 
Compartment