1 Overview
The wireless smoke detector features an onboard sounder, a smoke 
sensor, an LED indicator and local test capability to allow the user total 
visibility of its functionality. It is self-monitoring, alerting the user when 
sensor maintenance is needed or batteries are low, and automatically 
supervising the radio link.
The EN1244 and EN1244-60 wireless smoke detector have been designed 
for operation in the United States; the EN1244A wireless smoke detector 
has been designed for operation in Australia; and the EN1244Z wireless 
smoke detector has been designed for operation in New Zealand. 
The EN1244 wireless smoke detector is intended for open area protection 
and for connection to a compatible power supply or control unit for 
operation as part of a household fire alarm system (UL985).
Note: For  UL 2560 installations, refer to the EN6080 Area Control 
Gateway Installation Instructions
.
1.1 Maximum Number of Repeaters for a UL 2560 
Installation
To achieve the 99.99% alarm message reliability required for UL 2560 
compliance, system installations must operate within the following limits for 
end device and repeater counts.
1.2 
Inovonics Contact Information
If you have any problems with this procedure, contact Inovonics technical 
services:
• E-mail: support@inovonics.com.
• Phone: (800) 782-2709; (303) 939-9336.
1.3 Wireless Smoke Detector External Components
 Figure 1  Wireless smoke detector external components
Device Indicators
1.4 What’s In The Carton
• One 3V-Lithium battery, installed.
• Two drywall anchors.
• Two mounting screws.
2 Installation and Startup
2.1 Installation Notes
• These products are designed to be maintained by professional 
security technicians.
• Products are tested for indoor use.
• All products should be manually tested weekly.
2.2 Activate the Battery
1. Remove the orange dust cover.
Note: If the detector cover is loose it can detach while removing the dust 
cover. If the detector cover is removed with the orange dust cover, place 
End 
Devices
Maximum 
Repeaters
150
397
250
386
350
375
500
360
1000
313
2000
238
3000
184
For product and installation videos visit us at 
www.inovonics.com/videos or use the QR 
code below.
Green LED
Red LED
Sounder
Power up
Both LEDs 
blink every 5 
seconds
Both LEDs 
blink every 
5 seconds
Off
Normal 
(standby)
Blinks every 
10 seconds
Off
Off
Sensitivity out of 
range
Off
Blinks 
every five 
seconds
Off
Smoke alarm
Off
Lit
Temporal 
pattern
Low battery
Off
Blinks 
every 45 
seconds
Chirps every 
45 seconds 
beginning 
seven days 
after the LED 
begins 
blinking
Test 
button
Green 
LED
Red 
LED