Honeywell International Inc. RTU-L12 Manuel D’Utilisation
1.5.5 Output 1 – Door lock
The open collector output 1 (I max = 100mA) is used for door lock.
The open collector output 1 (I max = 100mA) is used for door lock.
An external DC relay must be installed in accordance with the following
limits:
• Max relay voltage = 28VDC
• Max relay current = 100mA
• Max Vce(sat at 100mA) = 1.2V
limits:
• Max relay voltage = 28VDC
• Max relay current = 100mA
• Max Vce(sat at 100mA) = 1.2V
It is mandatory to use the 1N4004 (or equivalent) provided diode in
parallel to the coil of the relay.
Inductive load with alternating current: not allowed
parallel to the coil of the relay.
Inductive load with alternating current: not allowed
VE
X
T
_r
el
è
GN
D
Rel
ay c
o
il
diode 1N4004
OUT1
Transient
suppressor
suppressor
Vd
c /
ac
V
d
c / ac
C
NC
N
O
E
le
ct
ro
lo
ck
co
il
Figure 10: Output 1connection – Door Lock
Page 14