SMC Networks SMCZB01 Manuel D’Utilisation

Page de 7
 
 
Copyright 
©
2010 SMC Networks
  
 
Page 1
 
All Rights Reserved 
 
I/M SMCSM01-Z rev. 1.0 
8/19/10 
1   
Unpacking 
Your SMCSM01-Z package includes the following items: 
 
One SMCSM01-Z Smoke Sensor 
 
One dust cover 
 
Two CR123A batteries 
 
Mounting bracket 
 
This user manual 
If any items are missing or damaged, contact your place of 
purchase. Keep the carton, including the original packing 
material, in case you need to store or return the product. 
 
2   
Specifications 
The SMCSM01-Z specifications are: 
 
Voltage: 3VDC  
 
Battery type1 3V Lithium, Duracell
®
 123, Sanyo
®
, and 
Panasonic
®
 CR123A 
 
Sensitivity  2.25 % ± 1.35 % 
 
Drift compensation adjustment  0.5%/ft. max 
 
Operating temperature: 40° to 100° F (4.4° and 37.8° C) 
 
Compatible control panel: RB5701-Z SMA Gateway 
The SMCSM01-Z specifications heat alarm specifications are: 
 
 Rate-of-rise: 15°F/min >105°F (8.3°C/min > 40.6°C) 
 
Fixed: 135°F ± 5°F (57.2°C ± 2.8°C) 
Note:
 
Constant exposures to high or low temperatures or 
high humidity may reduce battery life. 
 
3   
NFPA Guidelines 
 
NFPA 72, 2-1.4.2.1 Total (Complete) Coverage 
If required, total coverage shall include all rooms, halls, 
storage areas, basements, attics, lofts, spaces above 
suspended ceilings, and other subdivisions and accessible 
spaces; and the inside of all closets, elevator shafts, enclosed 
stairways, dumbwaiter shafts, and chutes. Inaccessible areas 
shall not be required to be protected by detectors. (For 
exceptions, refer to NFPA 72.)
 
 
NFPA 72, 2-1.4.2.2 Partial Coverage 
If required, partial detection systems shall be provided in all 
common areas and work spaces, such as corridors, lobbies, 
storage rooms, equipment rooms, and other tenantless spaces 
in those environments suitable for proper detector operation in 
accordance with this code.
 
 
NFPA 72, 2-1.4.2.3 Selective Coverage 
Where codes, standards, laws, or authorities having 
jurisdiction require the protection of selected areas only, the 
specified areas shall be protected in accordance with this 
code.
 
 
NFPA 72, 2-1.4.2.4 Supplementary (Non required) 
Coverage 
Where installed, detection that is not required by an 
applicable law, code, or standard, whether total (complete), 
partial, or selective coverage, shall conform to the 
requirements of this code. (For exceptions, refer to NFPA 72 
Chapter 2 Spacing Requirements.)
 
 
NFPA 72, 2-1.4.3 
Where non required detection devices are installed for a 
specific hazard, additional non required detection devices shall 
not be required to be installed throughout an entire room or 
building.
 
 
NFPA 72, 2-2 Heat-Sensing Fire Detectors 
Heat-sensing fire detectors shall be installed in all areas where 
required by the NFPA codes and standards or by the authority 
having jurisdiction.
 
 
NFPA 72, 8-1.4.1.3.2 Detection in New Apartment 
Buildings 
Approved, single-station smoke alarms shall be installed in 
accordance with 7-6.2.10 of NFPA 101 outside every sleeping 
area in the immediate vicinity of the bedrooms and on all 
levels of the dwelling unit including basements. (101: 18-
3.4.4.2) (For exceptions, refer to this section of NFPA 72.)
 
 
NFPA 72, 8-1.4.1.4.2 Detection in Existing Apartment 
Buildings Approved, single-station smoke alarms shall be 
in-stalled in accordance with 7-6.2.10 of NFPA 101 
outside every sleeping area in the immediate vicinity of 
the bedrooms and on all levels of the dwelling unit 
including basements. (101: 19-3.4.4.1) (For exceptions, 
refer to this section of NFPA 72.) 
 
4   
Technical Bulletin 
SMCSM01-Z is a member of SMC Networks’ family of reliable, 
high-quality products using the latest technology available. 
Please review the information in this section to ensure you 
get the most out of your new SMCSM01-Z Smoke Sensor. 
Pre-installation Considerations 
Install the SMCSM01-Z in accordance with the National Fire 
Protection Association’s (NFPA) Standard 72, Chapters 2 and 
8. Depending on the application, you may need to reference 
other chapters of NFPA 72 or NFPA 101. 
SMCSM01-Z Smoke Sensor User Manual 
Congratulations on purchasing your SMCSM01-Z Smoke Sensor. 
The SMCSM01-Z Smoke Sensor is a
 
low-profile wireless smoke detector designed to provide reliable smoke or fire detection. The SMCSM01-Z is ideal for difficult-to-wire 
residential or commercial applications. This user manual has all the information to get your SMCSM01-Z Smoke Sensor up and running quickly.  
 
continued on next page