Innovative Control Systems Inc IGWT-662008 Manuel D’Utilisation
B-2 Appendix Installation Manual
To test the Rx Supervise function, use the
following instructions:
following instructions:
1. At JP5, place the Jumper
in Position 1.
If LEDs 4, 5, and 14 blink once
every eight seconds, then the Rx
Supervise function is working
properly.
every eight seconds, then the Rx
Supervise function is working
properly.
If LEDs 4, 5, and 14 do not blink
once every eight seconds, then the
Rx Supervise function is NOT
working properly (
once every eight seconds, then the
Rx Supervise function is NOT
working properly (
see Appendix D-1
)
2. When done testing, at JP5, place the
Jumper in the desired interval
position.
position.
JP6 (Scan Rate)
Factory Default IN; Position 1-2
This jumper will set the Controller’s scan
speed for sequencing the Tx wand antennas.
Position 1-2 is better suited for detecting
persons who walk slowly through a zone.
Position 2-3 is better suited for detecting
persons who walk briskly through a zone.
For single antenna systems it is
recommended to use position 1-2.
speed for sequencing the Tx wand antennas.
Position 1-2 is better suited for detecting
persons who walk slowly through a zone.
Position 2-3 is better suited for detecting
persons who walk briskly through a zone.
For single antenna systems it is
recommended to use position 1-2.
JP7 (Extended Detection Delay)
Factory Default IN
This jumper will increase the time that a
valid Tag signal must be received before a
system response is initiated.
valid Tag signal must be received before a
system response is initiated.
JP8 (Detection Delay)
Factory Default IN; Position 1-2
This jumper extends the time required for
valid Tag detection. Keep the default setting.
valid Tag detection. Keep the default setting.
JP9 (External Reset)
Factory Default IN
This jumper selects which device will
control the resetting of the lock.
control the resetting of the lock.
Table B.4 JP9
Position Lock is reset using:
In Door
(Egress)
Alarm
Out
Time setting of switch S1
JP10 (Loiter Reset)
Factory Default IN
This jumper controls whether or not the
Loiter Alarm will be automatically reset.
Loiter Alarm will be automatically reset.
Table B.5 JP10
Position Alarm Automatically Resets?
In Yes
Out No
JP11 (Door Timer Extend Disable)
Factory Default IN
This jumper determines the timing range of
the Door Ajar Time potentiometer (R97).
the Door Ajar Time potentiometer (R97).
B.6 JP11
Position Time
Range
In 10-60
seconds
Out 65-110
seconds