Description
The Crestron
®
 GLS-LDL-EX-BATT is a battery-powered, wireless photo sensor designed 
for daylight harvesting applications to control the balance of natural and artificial lighting in 
an indoor space. Dual-loop sensing is achieved on the GLS-LDL-EX-BATT by two internal 
photocells—one for open-loop daylight sensing and one for closed-loop ambient light 
sensing.
Installation
NOTES:  Observe the following points:
  •  This product must be installed and used in accordance with appropriate electrical 
codes and regulations.
  •  This product must be installed by a qualified electrician.
  •  Sensors must be mounted on a vibration-free surface.
The GLS-LDL-EX-BATT must be installed so that it faces a window. The device should be 
installed approximately 4 to 6 feet (1.22 to 1.83 meters) away from the window. The 
optimum viewing angle for the open loop sensor is 35˚. The closed-loop viewing angle is 
straight down.
Additional Resources
Visit the product page on the Crestron website (www.crestron.com) 
for additional information and the latest firmware updates.
Arrow must point 
toward window.
Holes for mounting 
screws.
The base must be mounted to the drywall or drop ceiling using the provided anchors.
  1.  Determine the proper orientation for the GLS-LDL-EX-BATT.
  2.  Hold the base on the mounting surface, and use the holes for the mounting screws 
to mark the screw locations.
  3.  Using a 1/4 in drill bit, drill a pilot hole for the small anchor, and insert the small 
anchor into the pilot hole.
  4.  Using a #2 or #3 Phillips screwdriver, push the self-tapping anchor into the surface 
of the drywall until the cutting blades penetrate the surface. Using gentle forward 
pressure, rotate the anchor until the collar sets flush to the surface of the ceiling.
  5.  Secure the base to the mounting surface using two screws.
  6.  Place the sensor on the base and then rotate the sensor clockwise to secure it.
The sensor has the capability to rotate up to 40º along the base after it is mounted. Rotate 
the sensor so that it is perpendicular to the window.
Mount the Base
When mounting the base, ensure that the arrow on the base, shown below, points toward 
the desired window.
35°
Insert the Batteries
Insert the batteries into the back of the GLS-LDL-EX-BATT. The orientation of the batteries 
is indicated on the device.
Configuration
The GLS-LDL-EX-BATT is set up and configured during system commissioning. Refer to 
the SIMPL Windows help file for details.